PERFORMANCE DATA — 579F (cont)

ALTITUDE COMPENSATION* —

579F180-300

*Includes a 4% input reduction per each 1,000 feet.

†Orifices available through your Bryant distributor.

ALTITUDE DERATING FACTOR*

*Derating of the unit is not required unless the heating value of the gas

exceeds the values listed in the table above, or if the elevation
exceeds 6000 ft. Derating conditions must be 4% per thousand ft
above 2000 ft. For example, at 4000 ft, if the heating value of the gas
exceeds 1000 Btu/ft

3

, the unit will require a 16% derating. For eleva-

tions above 6000 ft, the same formula applies. For example, at 7000 ft,
the unit will require a 28% derating of the maximum heating value per
the National Fuel Gas Code.

IMPORTANT: Local utility companies may be reducing heat content of
gas at altitudes above 2000 ft. If this is being done, then changing
spuds may not be required.

Fan Performance Using Accessory Power Exhaust (579F180-300)

a50-4028

ELEVATION

(ft)

NATURAL GAS ORIFICE SIZE†

Low Heat

High Heat

0-3,000

30

29

3,000- 7,000

31

30

7,000- 9,000

32

31

9,000-10,000

33

31

above 10,000

35

32

ELEVATION (ft)

MAXIMUM HEATING VALUE

(Btu/ft

3

)

0-2,000

1,100

2,001-3,000

1,050

3,001-4,000

1,000

4,001-5,000

950

5,001-6,000

900

Advertising