PERFORMANCE DATA

COOLING CAPACITIES

Standard Ratings

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil.

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

580F036 (3 TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

900/0.11

1200/0.14

1500/0.17

Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

42.8

38.9

35.0

44.8

40.8

37.0

45.8

41.9

38.2

SHC

20.0

24.5

28.7

21.8

27.5

32.8

23.0

30.0

36.0

kW

2.91

2.81

2.70

2.99

2.88

2.78

3.02

2.92

2.82

85

TC

40.8

36.9

33.3

42.5

38.7

35.0

43.6

39.9

36.1

SHC

19.4

23.7

27.9

21.0

26.8

31.8

22.6

29.7

35.1

kW

3.14

3.01

2.90

3.20

3.08

2.97

3.24

3.14

3.02

95

TC

38.7

34.9

31.4

40.4

36.6

33.0

41.4

37.6

34.1

SHC

18.6

22.9

27.0

20.3

26.0

30.9

22.0

28.8

34.0

kW

3.35

3.21

3.09

3.42

3.29

3.16

3.47

3.35

3.22

105

TC

36.5

32.8

29.2

38.1

34.3

30.9

39.0

35.2

32.4

SHC

17.8

22.1

25.9

19.6

25.2

29.8

21.2

28.0

32.3

kW

3.55

3.41

3.27

3.63

3.49

3.35

3.68

3.54

3.43

115

TC

34.3

30.7

26.9

35.7

32.1

28.8

36.5

32.9

30.6

SHC

17.0

21.3

24.8

19.0

24.4

28.8

20.5

27.1

30.6

kW

3.76

3.60

3.45

3.84

3.68

3.54

3.88

3.74

3.64

580F048 (4 TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

1200/0.12

1600/0.15

2000/0.18

Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

57.9

53.1

48.3

60.4

55.9

51.3

62.2

57.3

52.9

SHC

27.2

33.3

39.2

29.4

37.2

44.8

31.4

40.3

49.1

kW

4.07

3.93

3.79

4.17

4.03

3.90

4.24

4.08

3.96

85

TC

55.7

50.8

45.3

57.7

53.4

48.5

59.4

55.0

50.2

SHC

26.4

32.5

37.8

28.4

36.7

43.6

30.5

40.3

47.9

kW

4.40

4.24

4.08

4.47

4.35

4.20

4.54

4.42

4.25

95

TC

52.9

48.1

42.5

55.2

50.5

45.7

56.7

52.0

47.4

SHC

25.5

31.5

36.4

27.6

35.6

42.2

29.7

39.2

46.7

kW

4.70

4.54

4.36

4.78

4.63

4.47

4.87

4.70

4.56

105

TC

50.1

45.3

39.8

52.3

47.6

42.8

53.6

48.9

44.9

SHC

24.4

30.3

35.1

26.7

34.5

40.7

28.8

38.1

44.6

kW

5.00

4.81

4.62

5.10

4.91

4.73

5.17

4.99

4.84

115

TC

47.3

42.6

37.2

49.3

44.6

40.0

50.5

45.9

42.4

SHC

23.4

29.2

33.7

25.9

33.3

39.3

27.8

37.1

42.4

kW

5.30

5.07

4.88

5.42

5.19

4.99

5.48

5.28

5.12

580F060 (5 TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

1500/0.07

2000/0.09

2500/0.12

Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

71.0

63.8

55.4

74.5

67.2

59.2

76.5

69.7

62.1

SHC

33.9

41.5

47.9

37.4

47.4

55.8

40.6

52.8

61.8

kW

5.04

4.82

4.62

5.20

4.97

4.76

5.29

5.06

4.87

85

TC

69.2

61.0

54.2

72.9

65.6

57.2

75.2

68.1

61.5

SHC

33.4

40.5

47.3

37.0

46.9

54.9

40.1

52.3

61.3

kW

5.50

5.27

5.02

5.66

5.41

5.18

5.75

5.50

5.29

95

TC

65.5

56.6

50.4

69.4

60.9

53.1

71.2

63.3

57.8

SHC

32.1

38.8

45.6

35.8

45.3

52.6

39.1

50.9

57.8

kW

5.88

5.62

5.37

6.01

5.76

5.53

6.12

5.87

5.67

105

TC

61.9

53.1

47.1

65.4

56.6

50.5

67.1

58.8

54.5

SHC

30.8

37.5

44.1

34.5

43.7

50.2

37.9

49.3

54.5

kW

6.25

5.99

5.72

6.38

6.13

5.91

6.50

6.23

6.06

115

TC

58.2

49.7

43.7

61.4

52.3

47.8

63.0

54.3

51.2

SHC

29.5

36.1

42.5

33.2

42.1

47.8

36.7

47.6

51.2

kW

6.63

6.35

6.08

6.75

6.49

6.29

6.88

6.59

6.46

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

Ldb — Leaving Dry-Bulb
Lwb — Leaving Wet-Bulb
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air leaving evaporator
coil (h

lwb

)

h

lwb

=

h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

58
0

F

03
6-

15
1

Advertising