Performance data, Cooling capacities, 239 performance data – Bryant 581C User Manual

Page 239: Cooling capacities — standard units

Advertising
background image

239

PERFORMANCE DATA

COOLING CAPACITIES — STANDARD UNITS

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-

rator coil (hlwb)

Where: hewb = Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

4. Use chart below for bypass factor.

581A155 (12 Tons)

Temp (F)

Air Ent

Cond

Evap Air — Cfm/BF

3600/0.01

4375/0.01

5000/0.01

Evap Air — Ewb (F)

54

58

62

67

72

76

80

54

58

62

67

72

76

80

54

58

62

67

72

76

80

60

TC

152

156

161

174

189

201

213

161

164

167

180

195

207

218

169

171

172

184

199

211

222

SHC

152

144

135

114

92.9

75.4

57.5

161

156

150

125

99.6

78.7

57.5

169

166

162

134

105

81.3

57.4

kW

7.56

7.65

7.74

8.01

8.33

8.6

8.86

7.76

7.82

7.88

8.14

8.46

8.72

8.97

7.92

7.95

7.98

8.24

8.55

8.82

9.06

70

TC

148

152

156

169

183

195

206

157

160

162

174

189

200

211

165

166

167

179

193

204

214

SHC

148

141

133

112

90.6

73.2

55.4

157

153

148

123

97.3

76.5

55.3

165

162

160

132

103

79.1

55.3

kW

8.5

8.58

8.67

8.97

9.26

9.53

9.8

8.7

8.75

8.81

9.07

9.39

9.66

9.91

8.86

8.89

8.91

9.16

9.49

9.76

9.99

75

TC

146

150

154

166

181

192

204

155

158

160

172

186

197

208

163

164

164

176

189

201

212

SHC

146

139

132

111

89.7

72.2

54.6

155

151

146

122

96.2

75.5

54.6

163

161

158

131

101

78.1

54.5

kW

9.02

9.1

9.18

9.45

9.8

10.1

10.4

9.22

9.27

9.31

9.58

9.91

10.2

10.5

9.39

9.41

9.43

9.68

9.99

10.3

10.6

85

TC

142

145

149

161

175

186

196

151

153

154

166

179

190

200

158

159

159

170

183

194

203

SHC

142

136

129

109

87.4

70

52.4

151

147

144

119

93.9

73.2

52.3

158

157

155

128

99.1

75.8

52.2

kW

10.1

10.2

10.3

10.6

10.9

11.2

11.5

10.3

10.4

10.4

10.7

11

11.3

11.6

10.5

10.5

10.5

10.8

11.1

11.4

11.7

95

TC

138

141

143

155

168

179

189

147

148

149

160

173

183

192

153

153

154

164

177

187

195

SHC

138

133

127

106

85

67.7

50.1

147

144

141

117

91.6

70.9

50

153

153

152

126

96.9

73.5

49.9

kW

11.4

11.4

11.5

11.8

12.2

12.4

12.7

11.6

11.6

11.6

11.9

12.3

12.6

12.8

11.8

11.8

11.8

12

12.4

12.7

12.9

105

TC

134

136

138

149

162

172

181

141

142

143

153

166

176

184

148

148

148

157

169

179

186

SHC

134

129

124

104

82.4

65.3

47.7

141

139

137

114

89

68.4

47.5

148

148

148

123

94.3

70.9

47.4

kW

12.7

12.8

12.8

13.2

13.5

13.8

14.1

12.9

13

13

13.3

13.6

13.9

14.2

13.1

13.1

13.1

13.4

13.7

14

14.3

115

TC

129

130

132

143

155

164

172

136

137

138

146

158

168

175

142

142

142

149

161

171

177

SHC

129

125

121

101

79.8

62.7

45.1

136

135

133

111

86.3

65.9

45

142

142

142

120

91.6

68.4

45

kW

14.2

14.2

14.3

14.6

15

15.3

15.6

14.4

14.4

14.5

14.7

15.1

15.5

15.7

14.6

14.6

14.6

14.8

15.2

15.6

15.7

125

TC

124

125

126

136

147

156

163

131

131

132

140

150

159

165

136

136

136

142

153

162

167

SHC

124

121

118

98.2

77

60.1

42.5

131

130

128

109

83.5

63.2

42.5

136

136

136

117

88.7

65.7

42.4

kW

15.8

15.8

15.9

16.2

16.6

17

17.2

16.1

16.1

16.1

16.4

16.7

17.1

17.3

16.3

16.2

16.2

16.4

16.8

17.2

17.4

581A155 (12 Tons) (cont)

Temp (F)

Air Ent

Cond

Evap Air — Cfm/BF

5625/0.02

6250/0.02

Evap Air — Ewb (F)

54

58

62

67

72

76

80

54

58

62

67

72

76

80

60

TC

175

175

176

187

202

214

224

180

180

180

190

204

216

226

SHC

175

173

171

142

110

83.8

57.3

180

180

180

151

115

86.2

57.2

kW

8.03

8.05

8.07

8.3

8.61

8.87

9.1

8.14

8.15

8.16

8.36

8.66

8.93

9.14

70

TC

170

171

171

181

195

207

216

175

176

176

184

198

209

218

SHC

170

169

168

140

108

81.5

55.2

175

176

176

148

113

84

55.1

kW

8.98

8.99

9.01

9.23

9.55

9.81

10

9.09

9.1

9.11

9.3

9.61

9.87

10.1

75

TC

168

168

169

179

192

203

213

173

173

173

181

195

206

215

SHC

168

167

166

139

107

80.5

54.4

173

173

173

147

112

83

54.3

kW

9.5

9.51

9.52

9.75

10.1

10.3

10.6

9.62

9.62

9.62

9.81

10.1

10.4

10.6

85

TC

163

163

164

172

185

196

205

168

168

168

175

188

198

206

SHC

163

162

162

136

104

78.2

52.2

168

168

168

145

109

80.6

52.1

kW

10.6

10.6

10.6

10.9

11.2

11.5

11.7

10.7

10.7

10.8

10.9

11.2

11.5

11.8

95

TC

158

158

158

166

178

189

196

162

162

162

168

180

190

197

SHC

158

157

157

134

102

75.9

49.8

162

162

162

142

107

78.3

49.7

kW

11.9

11.9

11.9

12.1

12.4

12.7

12.9

12

12

12

12.1

12.5

12.8

13

105

TC

152

152

152

159

171

181

187

157

157

157

161

173

182

188

SHC

152

152

152

131

99.3

73.3

47.4

157

157

157

139

104

75.7

47.4

kW

13.2

13.2

13.2

13.4

13.8

14.1

14.3

13.4

13.4

13.4

13.5

13.9

14.2

14.4

115

TC

146

146

146

151

163

172

177

150

150

150

153

165

174

178

SHC

146

146

146

128

96.6

70.7

44.9

150

150

150

136

102

73.1

44.8

kW

14.7

14.7

14.7

14.9

15.3

15.6

15.8

14.9

14.9

14.9

14.9

15.4

15.7

15.8

125

TC

140

140

140

144

155

163

167

144

144

144

146

156

164

168

SHC

140

140

140

125

93.7

67.9

42.4

144

144

144

133

98.7

70.2

42.3

kW

16.4

16.4

16.4

16.5

16.9

17.2

17.4

16.5

16.5

16.5

16.6

17

17.3

17.4

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

tldb = tedb –

sensible capacity (Btuh)

1.10 x cfm

hlwb = hewb –

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

CFM

ENTERING WET-BULB (F)

54

58

62

67

72

76

80

Bypass Factor

3600

0.355

0.158

0.054

0.038

0.049

0.000

0.000

4375

0.439

0.255

0.112

0.043

0.057

0.000

0.000

5000

0.486

0.314

0.126

0.054

0.037

0.000

0.000

5625

0.525

0.360

0.174

0.066

0.073

0.000

0.000

6250

0.551

0.410

0.202

0.080

0.079

0.000

0.000

58
1A15

5, 1

8

0

Advertising
This manual is related to the following products: