ELECTRICAL DATA — 581A (cont)

ELECTRICAL DATA — 581A155,180

LEGEND

*Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. Canadian units may be
fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent of volt-
age imbalance.
% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.

UNIT
581A

NOMINAL
VOLTAGE

(3 Ph, 60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

COMBUSTION

FAN MOTOR

POWER

SUPPLY

No. 1

No. 2

Min

Max

RLA

LRA

RLA

LRA

Qty

Hp

FLA (ea)

Hp

FLA

FLA

LRA

FLA

MCA

MOCP*

155

(Standard

IFM)

208/230

187

253

20.7

156

20.7

156

3

0.5

1.70

2.9

8.8/ 8.4

0.57

60/60

80/80

4.6

18.8

0.57

65/65

80/80

460

414

506

10.0

75

10.0

75

3

0.5

0.80

2.9

4.2

0.30

29

35

2.3

6.0

0.30

31

40

575

518

633

8.2

54

8.2

54

3

0.5

0.75

3.0

3.9

0.57

25

30

2.1

4.8

0.57

27

30

155

(Optional

IFM)

208/230

187

253

20.7

156

20.7

156

3

0.5

1.70

3.7 10.5/11.0

0.57

62/63

80/80

4.6

18.8

0.57

67/67

80/80

460

414

506

10.0

75

10.0

75

3

0.5

0.80

3.7

4.8

0.30

30

35

2.3

6.0

0.30

32

40

180

208/230

187

253

32.1

195

20.7

156

3

0.5

1.70

5.0

15.8/15.8

0.57

82/82

110/110

4.6

18.8

0.57

86/86

110/110

460

414

506

16.4

95

10.0

75

3

0.5

0.80

5.0

7.9

0.30

41

50

2.3

6.0

0.30

43

50

575

518

633

12.0

80

8.2

54

3

0.5

0.75

5.0

6.0

0.57

31

40

2.1

4.8

0.57

34

45

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

7
457