PERFORMANCE DATA — 579F

COOLING CAPACITIES

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

579F180 (15 Tons)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

4500

5250

Evaporator Air — Ewb (F)/BF

54/0.48

58/0.32

62/0.22

67/0.20

72/0.19

76/0.24

80/0.04

54/0.54

58/0.39

62/0.25

67/0.23

72/0.21

76/0.23

80/0.04

75

TC

168

177

192

209

225

240

171

171

182

197

214

229

246

SHC

152

142

123

103

85

69

171

150

151

130

108

88

69

kW

12.4

12.6

13.0

13.3

13.6

13.9

12.5

12.6

12.7

13.1

13.4

13.7

14.0

85

TC

159

164

171

186

202

219

233

166

172

175

190

207

222

237

SHC

159

148

139

120

100

83

66

166

151

148

127

105

86

67

kW

13.7

13.8

14.1

14.4

14.8

15.5

15.4

13.9

14.0

14.1

14.5

14.9

15.2

15.5

95

TC

154

159

165

179

195

210

226

161

164

169

183

199

214

229

SHC

154

142

136

117

98

80

64

161

155

145

124

102

83

64

kW

15.3

15.4

15.5

15.9

16.3

16.7

17.3

15.5

15.5

15.7

16.0

16.5

16.8

17.1

105

TC

149

154

158

172

187

201

216

156

156

162

176

191

205

222

SHC

149

137

133

114

95

78

61

156

156

142

121

99

81

62

kW

16.9

17.0

17.1

17.6

18.0

18.4

18.7

17.2

17.1

17.2

17.7

18.1

18.5

19.1

115

TC

144

145

152

165

179

193

207

150

151

156

168

183

196

210

SHC

144

142

130

111

92

75

58

150

151

137

118

96

78

58

kW

18.6

18.6

18.9

19.3

19.8

20.2

20.6

18.9

18.9

19.0

19.5

19.9

20.3

20.7

117

TC

143

143

150

163

178

191

205

149

149

154

167

181

194

208

SHC

143

142

129

110

91

74

57

149

149

136

117

96

77

58

kW

18.9

19.0

19.2

19.7

20.2

20.5

20.9

19.2

19.2

19.4

19.8

20.3

20.7

21.0

120

TC

141

141

148

161

175

147

148

152

164

179

SHC

141

141

128

109

90

147

148

135

116

95

kW

19.5

19.5

19.8

20.2

20.7

19.8

19.8

19.9

20.4

20.8

579F180 (15 Tons) (cont)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

6000

6750

Evaporator Air — Ewb (F)/BF

54/0.58

58/0.43

62/0.30

67/0.25

72/0.23

76/0.24

80/0.04

54/0.62

58/0.48

62/0.36

67/0.28

72/0.25

76/0.25

80/0.03

75

TC

178

174

185

200

218

233

250

183

179

183

203

221

236

253

SHC

178

171

159

136

112

91

70

183

179

161

142

116

93

70

kW

12.7

12.7

12.8

13.1

13.5

13.8

14.1

12.8

12.7

12.8

13.2

13.5

13.9

14.1

85

TC

173

173

179

193

210

227

244

178

178

183

196

213

228

247

SHC

173

172

156

133

109

89

68

178

178

161

139

113

91

68

kW

14.1

14.1

14.2

14.6

15.0

15.8

16.2

14.2

14.2

14.3

14.7

15.1

15.3

16.3

95

TC

167

167

173

186

203

217

232

173

173

177

189

205

220

235

SHC

167

167

152

130

106

86

64

173

173

157

137

111

88

65

kW

15.7

15.6

15.8

16.1

16.6

16.9

17.2

15.8

15.8

15.9

16.2

16.6

17.0

17.3

105

TC

162

162

167

179

194

208

223

168

167

171

181

197

211

225

SHC

162

162

147

127

104

83

61

168

167

152

133

108

85

62

kW

17.3

17.3

17.4

17.8

18.2

18.5

18.9

17.4

17.4

17.5

17.9

18.3

18.6

18.9

115

TC

156

156

160

171

186

199

213

160

160

165

173

188

201

215

SHC

156

156

143

124

101

80

59

160

160

145

130

104

82

59

kW

19.1

19.1

19.1

19.6

20.0

20.4

20.7

19.2

19.2

19.3

19.6

20.1

20.5

20.8

117

TC

154

155

159

169

184

197

211

159

159

163

171

186

199

SHC

154

155

142

124

100

79

58

159

159

144

129

104

82

kW

19.4

19.4

19.5

19.9

20.4

20.8

21.1

19.6

19.6

19.7

20.0

20.4

20.8

120

TC

153

153

157

167

181

157

157

161

169

SHC

153

153

140

122

99

157

157

142

128

kW

19.9

19.9

20.0

20.4

20.9

20.1

20.1

20.2

20.5

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb

Entering Wet-Bulb

kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

0.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

0.10

0.98

1.96

2.94

3.92

4.91

0.20

0.87

1.74

2.62

3.49

4.36

0.30

0.76

1.53

2.29

3.05

3.82

0.40

0.65

1.31

1.96

2.62

3.27

0.50

0.55

1.09

1.64

2.18

2.73

0.60

0.44

0.87

1.31

1.74

2.18

0.70

0.33

0.65

0.98

1.31

1.64

579

F18

0

-300