581a210-300 – Bryant 581C User Manual

Page 19

Advertising
background image

19

ARI* CAPACITY RATINGS — 581A210-300

LEGEND

*Air Conditioning and Refrigeration Institute.

†IPLV values are calculated based on control configuration T.CTL = 2

(2 Stage Y1).

**Size 300 unit is not listed with ARI, but is tested to ARI standards.

NOTES:

1. Rated in accordance with ARI Standards 360-93 and 270-95.
2. ARI ratings are net values, reflecting the effects of circulating fan heat.

3. Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and
95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F
db outdoor entering-air temperature.

4. All 581A210-300 units are in compliance with ASHRAE 90.1 2001 Energy

Standard for minimum EER requirements. Refer to state and local codes or
visit the following website: http://bcap-energy.org to determine if compliance
with this standard pertains to a given geographical area of the United States.

HEATING CAPACITIES AND EFFICIENCIES — 581A210-300

VERTICAL SUPPLY — NATURAL GAS

NOTE: All units are 2-stage gas heat.

HORIZONTAL SUPPLY — NATURAL GAS

*7000 cfm minimum recommended above 1.0 in. wg external static pressure.

NOTE: All units are 2-stage gas heat.

VERTICAL SUPPLY — PROPANE

NOTE: All units are 2-stage gas heat.

HORIZONTAL SUPPLY — PROPANE

*7000 cfm minimum recommended above 1.0 in. wg external static pressure.
NOTE: All units are 2-stage gas heat.

UNIT
581A

NOMINAL

TONS

CFM

NET COOLING

CAPACITY (Btuh)

TOTAL

kW

EER

SOUND RATING

(dB)

IPLV†

210

18

5,500

200,000

18.5

10.8

81.7

12.0

240

20

6,000

234,000

21.7

10.8

81.7

11.9

300**

25

7,500

278,000

27.8

10.0

84.6

10.9

db

Dry Bulb

EER — Energy Efficiency Ratio
IPLV — Integrated Part-Load Values
wb

Wet Bulb

UNIT
581A

HEATING INPUT

(Btuh) Stage 2/Stage 1

OUTPUT CAPACITY

(Btuh)

TEMPERATURE

RISE (F)

STEADY-STATE

EFFICIENCY %

MINIMUM

HEATING CFM

210250

250,000/199,000

205,000

15-45

82%

4218

210365

365,000/281,000

296,000

25-55

81%

4977

210400

400,000/317,000

328,000

25-55

82%

5522

240250

250,000/199,000

205,000

15-45

82%

4218

240365

365,000/281,000

296,000

25-55

81%

4977

240400

400,000/317,000

328,000

25-55

82%

5522

300250

250,000/199,000

205,000

15-45

82%

4218

300365

365,000/281,000

296,000

25-55

81%

4977

300400

400,000/317,000

328,000

25-55

82%

5522

UNIT
581A

HEATING INPUT

(Btuh) Stage 2/Stage 1

OUTPUT CAPACITY

(Btuh)

TEMPERATURE

RISE (F)

STEADY-STATE

EFFICIENCY %

MINIMUM

HEATING CFM

210250

250,000/199,000

205,000

15-45

82%

4218

210365

365,000/281,000

296,000

25-55

81%

4977

210400

400,000/317,000

328,000

25-55

82%

5522

240250

250,000/199,000

205,000

15-45

82%

4218

240365

365,000/281,000

296,000

25-55

81%

4977

240400

400,000/317,000

328,000

25-55

82%

5522

300250

250,000/199,000

205,000

15-45

82%

4218

300365

365,000/281,000

296,000

25-55

81%

4977*

300400

400,000/317,000

325,000

25-55

82%

5522*

UNIT
581A

HEATING INPUT

(Btuh) Stage 2/Stage 1

OUTPUT CAPACITY

(Btuh)

TEMPERATURE

RISE (F)

STEADY-STATE

EFFICIENCY %

MINIMUM

HEATING CFM

210250

250,000/207,000

205,000

15-45

82%

4218

210365

365,000/291,000

296,000

25-55

81%

4480

210400

400,000/331,000

328,000

25-55

82%

5522

240250

250,000/207,000

205,000

15-45

82%

4218

240365

365,000/291,000

296,000

25-55

81%

4480

240400

400,000/331,000

328,000

25-55

82%

5522

300250

250,000/207,000

205,000

15-45

82%

4218

300365

365,000/291,000

296,000

25-55

81%

4480

300400

400,000/331,000

328,000

25-55

82%

5522

UNIT
581A

HEATING INPUT

(Btuh) Stage 2/Stage 1

OUTPUT CAPACITY

(Btuh)

TEMPERATURE

RISE (F)

STEADY-STATE

EFFICIENCY %

MINIMUM

HEATING CFM

210250

225,000/207,000

185,000

15-45

82%

3807

210365

329,000/291,000

266,000

25-55

81%

4480

210400

356,000/331,000

292,000

25-55

82%

4916

240250

225,000/207,000

184,500

15-45

82%

3796

240365

329,000/291,000

266,000

25-55

81%

4480

240400

356,000/331,000

292,000

25-55

82%

4916

300250

225,000/207,000

185,000

15-45

82%

3807

300365

329,000/291,000

266,000

25-55

81%

4480*

300400

356,000/331,000

292,000

25-55

82%

4920*