579f180-300, Physical data – Bryant 581C User Manual

Page 175

Advertising
background image

175

PHYSICAL DATA — 579F180-300

LEGEND

*Circuit 1 uses the lower portion of condenser coil and lower portion of evapora-

tor coils; and Circuit 2 uses the upper portion of both coils.

†Rollout switch is manual reset.

**The 579F300 units requires 2-in. industrial-grade filters capable of handling face

velocities of up to 625 ft/min (such as American Air Filter no. 5700 or equivalent).

NOTE: The 579F units have a low-pressure switch (standard) located on the suc-
tion side.

UNIT 579F

180

216

240

300

208/230, 460 v

575 v

NOMINAL CAPACITY (tons)

15

18

20

25

OPERATING WEIGHT (lb)

1650

1800

1850

2000

Economizer

90

90

90

90

Roof Curb

200

200

200

200

COMPRESSOR

Scroll

Quantity...Model (Ckt 1, Ckt 2)

2...SR*942AE

2

90, 90

1...SM120,

1...SR*782AE

1...SM120,

1...SM110

1...SM161,

1...SM120

Number of Refrigerant Circuits

2

2

2

Oil (oz) (Ckt 1, Ckt 2)

110, 72

110,110

112, 110

Stages of Capacity Control (%)

50/50

60/40

52/48

56/44

REFRIGERANT TYPE

R-22

Expansion Device

TXV

Operating Charge (lb-oz)
Circuit 1*

10-13

10-5

15-2

16-3

21-0

Circuit 2

11-5

14-8

15-4

CONDENSER COIL

Cross-Hatched

3

/

8

-in. Copper Tubes, Aluminum Lanced,

Aluminum Pre-Coated, or Copper Plate Fins

Rows...Fins/in.

2...17

21.7

3...15

3...15

4...15

Total Face Area (sq ft)

21.7

21.7

21.7

CONDENSER FAN

Propeller Type

Nominal Cfm

10,400

9300

13,700

12,500

Quantity...Diameter (in.)

3...22

3...22

2...30

2...30

Motor Hp...Rpm

1

/

2

...1050

1

/

2

...1050

1...1075

1...1075

Watts Input (Total)

1100

1100

3400

3400

EVAPORATOR COIL

Cross-Hatched

3

/

8

-in. Copper Tubes, Aluminum Lanced or

Copper Plate Fins, Face Split

Rows...Fins/in.

2...17

3...15

3...15

4...15

Total Face Area (sq ft)

17.5

17.5

17.5

17.5

EVAPORATOR FAN

Centrifugal Type

Quantity...Size (in.)

2...10 x 10

2...10 x 10

2...12 x 12

2...12 x 12

2...12 x 12

Type Drive

Belt

Belt

Belt

Belt

Belt

Nominal Cfm

6000

6000

7200

8000

10,000

Motor Hp

3.7

3.0

5

7.5

10

Motor Nominal Rpm

1725

1725

1745

1745

1740

Maximum Continuous Bhp

4.25

3.45

5.90

8.7 [208/230, 575 v]

9.5 [460 v]

10.2 [208/230, 575 v]

11.8 [460 v]

Motor Frame Size

56H

56H

184T

213T

215T

Nominal Rpm High/Low

Fan r/s Range

Low-Medium Static

891-1179

1159-1429

910-1095

1002-1225

1066-1283

High Static

1227-1550

1069-1287

1193-1458

1332-1550

Motor Bearing Type

Ball

Ball

Ball

Ball

Ball

Maximum Allowable Rpm

1550

1550

1550

1550

1550

Motor Pulley Pitch Diameter

Low-Medium Static

3.1/4.1

4.3/5.3

4.9/5.9

5.4/6.6

4.9/5.9

Min/Max (in.)

High Static

3.7/4.7

4.9/5.9

5.4/6.6

4.9/5.9

Nominal Motor Shaft Diameter (in.)

7

/

8

7

/

8

1

1

/

8

1

3

/

8

1

3

/

8

Fan Pulley Pitch Diameter (in.)

Low-Medium Static

6.0

6.4

9.4

9.4

8.0

High Static

5.2

8.0

7.9

6.4

Nominal Fan Shaft Diameter (in.)

1

3

/

16

1

3

/

16

1

7

/

16

1

7

/

16

1

7

/

16

Belt, Quantity...Type...Length (in.)

Low-Medium Static

1...BX...42

1...BX...45

1...BX...50

1...BX...54

2...BX...50

High Static

1...BX...42

1...BX...48

1...BX...50

2...BX...47

Pulley Center Line Distance (in.)

13.5-15.5

13.5-15.5

13.3-14.8

14.6-15.4

14.6-15.4

Speed Change per Full Turn of

Movable Pulley Flange (rpm)

Low-Medium Static

48

44

37

37

36

High Static

55

34

44

45

Movable Pulley Maximum Full Turns

From Closed Position

5

5

5

5

5

Factory Speed

3.5

3.5

3.5

3.5

3.5

Factory Speed Setting (rpm)

Low-Medium Static

1035

1296

1002

1120

1182

High Static

1389

1178

1328

1470

Fan Shaft Diameter at Pulley (in.)

1

3

/

16

1

3

/

16

1

7

/

16

1

7

/

16

1

7

/

16

Bhp

Brake Horsepower

TXV

Thermostatic Expansion Valve

579

F18

0

-300

Advertising