Sound data, Electrical data, 165 sound data – Bryant 581C User Manual

Page 165: Performance data — 581c

Advertising
background image

165

SOUND DATA

LEGEND

ARI Air Conditioning and Refrigeration Institute

NOTE: Indoor sound power is available in Bryant’s Electronic Catalog Program (ECAT) for
specific operating parameters.

PERFORMANCE DATA — 581C

581C024-036

LEGEND

*The values listed in this table do not include power exhaust. See table at right

for power exhaust requirements.

**Fuse or HACR circuit breaker.

†460v motor

NOTES:

1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. The UL, Canada units
may be fuse or circuit breaker.

2. Electrical data based on 95 F ambient outdoor-air temperature ± 10%

voltage.

3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent of volt-
age imbalance.

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

POWER EXHAUST ELECTRICAL DATA

* — Single or three phase rooftop unit
N/A — Not available
NOTE: If a single power source is to be used, size wire to include power
exhaust MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit.
Determine the new MCA including the power exhaust using the following
formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 581B060—unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A01 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would
not change. The MOCP in this example is 35 amps and the MCA New is
below 35; therefore the MOCP is acceptable. If “MCA New” is larger than
the published MOCP, raise the MOCP to the next larger size. For separate
power, the MOCP for the power exhaust will be 15 amps per NEC.

UNIT
581C

ARI

RATING

(decibels)

A-WEIGHTED

(db)

OCTAVE BANDS

63

125

250

500

1000 2000 4000 8000

024-048

76

76.0

55.9 66.0 64.0 66.2

68.4

64.5

61.7

57.3

060

80

80.0

59.1 68.9 68.7 71.9

74.0

68.9

65.7

59.0

UNIT

SIZE

NOMINAL

V-PH-Hz

IFM TYPE

VOLTAGE

RANGE COMPRESSOR

OFM

COMBUSTION

FAN MOTOR

IFM

CONV

OUTLET

POWER SUPPLY

*

MINIMUM UNIT

DISCONNECT

SIZE

Min Max QTY

RLA LRA

QTY

FLA

FLA

FLA

MCA

MOCP
**

FLA LRA

024

(2 tons)

208/

230-1-60

STD

187

254

1

10.9

63

1

0.7

0.6

2.0

NO

16.3

20

15.6

69

YES

22.3

25

21.2

73

036

(3 tons)

208/

230-1-60

STD

187

254

1

16

88

1

0.7

0.6

4.9

NO

25.6

30

24.8

101

YES

31.6

35

30.4

106

208/

230-3-60

STD

187

254

1

10.3

77

1

0.7

0.6

4.9

NO

18.5

25

18.3

90

YES

24.5

30

23.8

95

HS

5.8

NO

19.4

25

19.3

120

YES

25.4

30

24.9

124

460-3-60

STD

414

508

1

5.1

39

1

0.4

0.3

2.2

NO

9.0

15

8.9

46

YES

11.7

15

11.4

48

HS

2.6

NO

9.4

15

9.3

60

YES

12.1

15

11.8

63

575-3-60

STD

518

632

1

4.2

31

1

0.4

0.3†

1.9

NO

7.6

10

7.5

36

YES

9.7

15

9.5

38

HS

2.0

NO

7.7

10

7.6

43

YES

9.8

15

9.6

44

Perfect Humidity

1

0.4†

2.6†

NO

7.7

10

8.0

48

YES

9.8

15

9.6

50

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

UL

Underwriters’ Laboratories

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

= 457

% Voltage Imbalance = 100 x

7

457

= 1.53%

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.

POWER EXHAUST

PART NO.

Application

usage

MCA

(230 v)

MCA

(460 v)

MCA

(575 v)

MOCP

(for

separate

power

source)

CRPWREXH030A01

036-072

1.6

N/A

0.64

15

CRPWREXH021A01

036-072

N/A

0.68

N/A

15

CRPWREXH028A01

ALL*

1.7

N/A

0.68

15

CRPWREXH029A01

ALL

N/A

0.7

N/A

15