581b036-150, Physical data, 581b036-072 – Bryant 581C User Manual

Page 87

Advertising
background image

87

PHYSICAL DATA — 581B036-072

LEGEND

*Single phase/three phase.

†Indicates automatic reset.

**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and

120,000 Btuh heat input units have 3 burners. 115,000 Btuh heat input units
and 150,000 Btuh Heat input units have 3 burners.

††An LP kit is available as an accessory.

||California compliant three-phase models.

***California SCAQMD compliant low NO

x

models have combustion products that

are controlled to 40 nanograms per joule or less.

UNIT SIZE 581B

036

048

060

072

NOMINAL CAPACITY

3

4

5

6

OPERATING WEIGHT (lb)

Unit

530

540

560

635

COMPRESSOR

Scroll

Quantity

1

1

1

1

Oil (oz)

42

53

50

60

REFRIGERANT TYPE

R-22

Operating Charge (lb-oz)
Standard Unit

5-8

10-2

10- 0

12-8

Unit With Perfect Humidity Dehumidification Package

9-0

15-8

17-0

21-0

CONDENSER FAN

Propeller

Quantity...Diameter (in.)

1...22

1...22

1...22

1...22

Nominal Cfm

3500

3500

4100

4100

Motor Hp...Rpm

1

/

4

...825

1

/

4

...825

1

/

4

...1100

1

/

4

...1100

Watts Input (Total)

180

180

320

320

CONDENSER COIL

3

/

8

-in. OD Enhanced Copper Tubes, Aluminum Lanced Fins

Standard Unit

Rows...Fins/in.

1...17

2...17

2...17

2...17

Total Face Area (sq ft)

14.6

16.5

16.5

16.5

Unit with Perfect Humidity Dehumidification Package

Rows...Fins/in.

1...17

1...17

1...17

1...17

Total Face Area (sq ft)

3.9

3.9

3.9

3.9

EVAPORATOR COIL

3

/

8

-in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Metering Device

Rows...Fins/in.

2...15

2...15

4...15

4...15

Total Face Area (sq ft)

5.5

5.5

5.5

5.5

EVAPORATOR FAN

Centrifugal Type, Belt Drive

Quantity...Size (in.)

1...10 x 10

1...10 x 10

1...10 x 10

1...10 x 10

Nominal Cfm

1200

1600

2000

2400

Maximum Continuous Bhp

Std

1.20

1.20

1.30/2.40*

2.40

Hi-Static

2.40

2.40

2.90

2.90

Motor Frame Size

Std

48

48

48/56*

56

Hi-Static

56

56

56

56

Fan Rpm Range

Std

680-1044

770-1185

1035-1460

1119-1585

Hi-Static

1075-1455

1075-1455

1300-1685

1300-1685

Motor Bearing Type

Ball

Ball

Ball

Ball

Maximum Fan Rpm

2100

2100

2100

2100

Motor Pulley Pitch Diameter A/B (in.)

Std

1.9/2.9

1.9/2.0

2.4/3.4

2.4/3.4

Hi-Static

2.8/3.8

2.8/3.8

3.4/4.4

3.4/3.4

Nominal Motor Shaft Diameter (in.)

Std

1

/

2

1

/

2

5

/

8

5

/

8

Hi-Static

5

/

8

5

/

8

5

/

8

7

/

8

Fan Pulley Pitch Diameter (in.)

Std

4.5

4.0

4.0

3.7

Hi-Static

4.5

4.5

4.5

4.5

Belt — Type...Length (in.)

Std

1...A...36

1...A...36

1....4...40

1...A...38

Hi-Static

1...A...39

1...A...39

1...A...40

1...A...40

Pulley Center Line Distance (in.)

10.0-12.4

10.0-12.4

14.7-15.5

14.7-15.5

Speed Change per Full Turn of

Movable Pulley Flange (rpm)

Std

65

70

75

95

Hi-Static

65

65

60

60

Movable Pulley Maximum Full

Turns from Closed Position

Std

5

5

6

5

Hi-Static

6

6

5

5

Factory Setting — Full Turns Open

Std

3

3

3

3

Hi-Static

3

1

/

2

3

1

/

2

3

1

/

2

3

1

/

2

Factory Speed Setting (rpm)

Std

826

936

1248

1305

Hi-Static

1233

1233

1396

1396

Fan Shaft Diameter at Pulley (in.)

5

/

8

5

/

8

5

/

8

5

/

8

Bhp — Brake Horsepower

5

81B0

36-

15
0

Advertising
This manual is related to the following products: