Electrical data, 79 electrical data – Bryant 581C User Manual

Page 79

Advertising
background image

79

ELECTRICAL DATA

LEGEND

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer

to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local
electric utility company immediately.

3. For units with power exhaust: If a single power source is to be used, size wire to include

power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered
through the unit (must be in accordance with NEC and/or local codes). Determine the new
MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A01 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is
acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next
larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

POWER EXHAUST ELECTRICAL DATA

*Single or three phase.

UNIT SIZE

580F

NOMINAL

V-PH-Hz

IFM

TYPE

CONV

OUTLET

VOLTAGE

RANGE

COMPRESSOR (each)

OFM (each)

IFM
FLA

COMBUSTION

FAN MOTOR

POWER SUPPLY

MINIMUM UNIT

DISCONNECT SIZE*

Min

Max

Qty

RLA

LRA

Qty

FLA

FLA

MCA

MOCP†

FLA

LRA

036

(3 Ton)

208/230-3-60

STD

NO

187

254

1

10.2

75

1

1.4

3.5

0.6

17.7

25

17

85

YES

23.7

25

23

90

ALT

NO

4.9

19.1

25

19

90

YES

25.1

30

25

95

HIGH

NO

5.2

19.4

25

19

109

YES

25.4

30

25

114

460-3-60

STD

NO

414

508

1

4.4

40

1

0.8

1.3

0.3

7.6

15

7

44

YES

10.3

15

10

47

ALT

NO

2.1

8.4

15

8

48

YES

11.1

15

11

50

HIGH

NO

2.6

8.9

15

9

57

YES

11.6

15

11

59

575-3-60

ALT

NO

518

632

1

3.7

31

1

0.6

1.9

0.3

7.1

15

7

37

YES

9.3

15

9

39

HIGH

NO

2.0

7.2

15

8

44

YES

9.4

15

10

45

048

(4 Ton)

208/230-3-60

STD

NO

187

254

1

15.4

90

1

1.4

3.5

0.6

24.2

30

23

101

YES

30.2

35

29

106

ALT

NO

4.9

25.6

30

25

105

YES

31.6

35

30

110

HIGH

NO

5.2

25.9

30

25

124

YES

31.9

35

31

129

460-3-60

STD

NO

414

508

1

8.3

45

1

0.8

1.8

0.3

13.0

20

13

51

YES

15.7

20

15

53

ALT

NO

2.1

13.3

20

13

53

YES

16.0

20

15

55

HIGH

NO

2.6

13.8

20

13

62

YES

16.5

20

16

64

575-3-60

ALT

NO

518

632

1

6.4

36

1

0.6

1.9

0.3

10.5

15

10

42

YES

12.7

15

12

43

HIGH

NO

2.0

10.6

15

10

49

YES

12.8

15

12

50

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

% Voltage Imbalance = 100 x

7

457

POWER EXHAUST

PART NO.

APPLICATION

USAGE

MCA

(230 V)

MCA

(460 V)

MCA

(575 V)

MOCP

(separate

power source

only)

CRPWREXH030A01

036-073*

1.6

N/A 0.64

15

CRPWREXH021A01

036-073

N/A 0.68

N/A

15

CRPWREXH022A01

090-151*

3.4

N/A 1.32

15

CRPWREXH023A01

090-151

N/A 1.4

N/A

15

CRPWREXH028A01

ALL*

1.7

N/A 0.68

15

CRPWREXH029A01

ALL

N/A 0.7

N/A

15

58
0

F

03
6-

15
1