PERFORMANCE DATA

COOLING CAPACITIES, STANDARD UNITS

Standard Ratings

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil.

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B036 (3 TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

900/0.14

1200/0.17

1500/0.20

Air Entering Evaporator — Ewb

72

67

62

72

67

62

72

67

62

75

TC

41.9

38.7

35.7

43.5

40.8

37.7

44.8

41.8

39.0

SHC

20.4

25.2

29.7

21.8

28.2

33.8

23.3

30.7

37.0

kW

2.19

2.16

2.12

2.21

2.18

2.15

2.23

2.19

2.16

85

TC

40.7

37.5

34.5

42.1

39.3

36.4

43.5

40.4

37.6

SHC

19.9

24.7

29.2

21.5

27.7

33.2

23.2

30.3

36.4

kW

2.46

2.42

2.39

2.47

2.44

2.41

2.50

2.45

2.42

95

TC

39.3

36.1

33.1

40.8

37.8

34.9

42.0

38.9

36.1

SHC

19.5

24.1

28.4

21.1

27.2

32.5

22.8

29.9

35.6

kW

2.75

2.71

2.66

2.77

2.73

2.69

2.79

2.74

2.71

105

TC

37.7

34.6

31.7

39.3

36.2

33.4

40.1

37.2

34.7

SHC

18.8

23.5

27.8

20.7

26.6

31.8

22.1

29.3

34.7

kW

3.06

3.02

2.98

3.09

3.04

3.01

3.10

3.06

3.03

115

TC

36.0

33.0

29.7

37.4

34.5

31.5

38.1

35.5

33.2

SHC

18.3

22.9

26.7

19.9

26.1

30.9

21.3

28.7

33.2

kW

3.41

3.36

3.31

3.43

3.39

3.34

3.44

3.41

3.37

125

TC

34.2

31.3

27.8

35.6

32.7

29.4

36.3

33.6

31.9

SHC

17.6

22.2

25.8

19.4

25.4

29.4

20.8

28.0

31.8

kW

3.78

3.73

3.66

3.80

3.76

3.71

3.81

3.78

3.75

581B048 (4 TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

1200/0.17

1450/0.19

1600/0.21

2000/0.24

Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

54.0

50.7

44.2

55.9

52.2

47.7

56.4

52.8

49.1

58.1

54.5

50.6

SHC

26.1

32.7

37.5

27.6

35.1

41.8

28.2

36.2

43.8

30.2

39.5

47.5

kW

2.81

2.80

2.76

2.83

2.81

2.78

2.83

2.80

2.79

2.84

2.82

2.79

85

TC

52.2

48.9

41.9

54.1

50.4

45.9

54.5

51.0

47.2

55.3

52.3

48.7

SHC

25.4

32.0

36.4

26.9

34.5

40.8

27.5

35.7

42.8

28.6

38.5

46.6

kW

3.20

3.19

3.15

3.22

3.20

3.17

3.22

3.20

3.18

3.22

3.20

3.18

95

TC

50.7

46.9

39.5

51.9

48.4

43.5

52.5

48.9

45.2

53.9

50.1

46.7

SHC

24.9

31.1

35.0

26.1

33.6

39.6

26.8

34.7

41.8

28.8

37.5

45.6

kW

3.64

3.61

3.57

3.65

3.62

3.60

3.65

3.62

3.60

3.67

3.63

3.61

105

TC

48.8

44.5

36.7

49.8

46.2

40.7

50.2

46.7

42.1

51.5

48.2

44.7

SHC

24.3

30.2

33.6

25.3

32.8

38.2

26.0

33.9

40.3

27.9

37.4

44.4

kW

4.12

4.09

4.03

4.12

4.09

4.06

4.12

4.09

4.07

4.14

4.11

4.08

115

TC

46.5

41.1

34.3

47.7

43.3

37.0

48.0

44.4

38.5

48.9

45.7

42.0

SHC

23.4

28.9

32.4

24.9

31.8

36.3

25.4

33.4

38.3

27.1

36.9

42.0

kW

4.64

4.59

4.53

4.65

4.62

4.55

4.64

4.63

4.56

4.65

4.63

4.60

125

TC

43.8

37.5

32.4

45.1

39.0

33.8

45.3

40.1

35.4

46.3

42.6

38.8

SHC

22.5

27.4

31.5

24.1

30.2

33.7

24.7

31.9

35.4

26.5

35.9

38.8

kW

5.19

5.13

5.05

5.20

5.15

5.09

5.19

5.17

5.11

5.20

5.19

5.15

581B060 (5 TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

1500/0.08

1750/0.09

2000/0.11

2500/0.13

Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

70.8

65.4

58.5

72.5

67.3

61.1

73.0

68.4

62.8

74.8

70.3

64.8

SHC

34.1

42.7

49.9

35.7

45.5

54.2

36.8

48.0

57.8

39.6

53.0

63.4

kW

3.53

3.49

3.44

3.55

3.50

3.46

3.55

3.51

3.47

3.57

3.54

3.48

85

TC

68.9

63.2

55.3

70.5

65.1

57.9

72.2

66.4

60.2

73.2

68.1

62.9

SHC

33.5

41.8

48.4

35.0

44.8

52.8

37.0

47.6

56.8

39.3

52.5

62.4

kW

3.98

3.94

3.87

4.00

3.96

3.90

4.03

3.97

3.92

4.04

3.99

3.94

95

TC

66.8

60.6

52.4

68.3

62.5

54.3

69.3

63.8

56.6

71.2

65.6

60.6

SHC

32.8

40.7

47.0

34.5

43.8

51.1

36.0

46.7

55.0

39.1

51.8

60.5

kW

4.48

4.43

4.35

4.50

4.45

4.37

4.51

4.46

4.40

4.55

4.48

4.44

105

TC

64.3

57.7

49.9

65.9

59.8

51.7

66.9

61.1

54.1

68.4

62.8

58.4

SHC

32.0

39.6

45.8

33.7

42.8

49.7

35.3

45.7

53.5

38.4

51.0

58.4

kW

5.03

4.96

4.87

5.05

4.99

4.90

5.06

5.00

4.93

5.08

5.02

4.98

115

TC

61.5

54.8

47.3

62.8

56.7

49.1

64.0

58.2

51.6

65.4

59.9

56.1

SHC

31.0

38.4

44.5

32.5

41.6

48.2

34.4

44.6

51.6

37.4

50.0

56.1

kW

5.61

5.55

5.46

5.62

5.58

5.49

5.65

5.60

5.52

5.67

5.61

5.57

125

TC

58.7

51.6

44.5

59.9

53.4

46.2

60.8

54.9

49.0

62.2

56.8

53.5

SHC

30.0

37.2

43.1

31.7

40.4

46.2

33.3

43.4

48.9

36.4

48.9

53.4

kW

6.27

6.19

6.09

6.28

6.21

6.13

6.29

6.24

6.17

6.31

6.27

6.22

BF

Bypass Factor

Edb

Entering Dry Bulb

Ewb

Entering Wet Bulb

kW

Compressor Motor Power Input

SHC

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air leaving
evaporator coil (h

lwb

)

h

lwb

=

h

ewb

total capacity (Btuh)

4.5 x cfm

581

B0

36

-15

0