PERFORMANCE DATA (cont)

ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 580F180-300

LEGEND

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be

used in conjunction with the Fan Performance tables to determine blower rpm and watts.

FAN RPM AT MOTOR PULLEY SETTINGS*

*Approximate fan rpm shown.

†Indicates standard drive package.

**Indicates alternate drive package.

††Due to belt and pulley size, pulley cannot be set to this number of turns open.

EVAPORATOR-FAN MOTOR PERFORMANCE

LEGEND

*Extensive motor and electrical testing on these units ensures that the full horse-

power (brake kilowatt) range of the motors can be utilized with confidence. Using
your fan motors up to the horsepower (brake kilowatt) ratings shown in this table

will not result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.

NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency require-
ments as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.

EVAPORATOR-FAN MOTOR EFFICIENCY

NOTE: The EPACT (Energy Policy Act of 1992) regulates energy
requirements for specific types of indoor fan motors. Motors regulated
by EPACT include any general purpose, T-frame (three-digit, 143 and
larger), single-speed, foot mounted, polyphase, squirrel cage induction
motors of NEMA (National Electrical Manufacturers Association) design
A and B, manufactured for use in the United States. Ranging from 1 to
200 Hp, these continuous-duty motors operate on 230 and 460 volt,
60 Hz power. If a motor does not fit into these specifications, the motor
does not have to be replaced by an EPACT-compliant energy-efficient
motor. Variable-speed motors are exempt from EPACT compliance
requirements. Therefore, the indoor-fan motors for these units are
exempt from these requirements.

COMPONENT

CFM

4500

5000

5400

6000

7200

7500

9000

10,000

11,250

EconoMi$er IV and EconoMi$er2

0.040

0.050

0.060

0.070

0.090

0.100

0.110

0.120

0.140

FIOP

Factory-Installed Option

UNIT
580F

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

180†

††

††

††

††

1021

1002

984

965

947

928

910

891

873

180**

††

††

††

††

1200

1178

1156

1134

1112

1091

1069

1047

1025

210†

††

††

1095

1077

1058

1040

1021

1002

984

965

947

928

910

210**

††

††

1287

1265

1243

1222

1200

1178

1156

1134

1112

1091

1069

240†

††

††

††

††

1151

1132

1114

1095

1077

1058

1040

1021

1002

240**

††

††

††

††

1369

1347

1325

1303

1281

1259

1237

1215

1193

300†

††

††

1283

1269

1247

1225

1203

1182

1160

1138

1116

1095

1066

300**

††

††

††

††

1551

1524

1497

1470

1443

1415

1388

1361

1332

UNIT
580F

UNIT

VOLTAGE

MAXIMUM

ACCEPTABLE
CONTINUOUS

BHP*

MAXIMUM

ACCEPTABLE
CONTINUOUS

BkW*

MAXIMUM

ACCEPTABLE

OPERATING

WATTS

MAXIMUM

AMP DRAW

180

208/230

6.13

4.57

5,180

15.8

460

7.9

575

6.0

210

208/230

5.90

4.40

5,180

15.8

460

7.9

575

6.0

240

208/230

8.70

6.49

7,915

22.0

460

9.50

7.08

8,640

13.0

575

8.70

6.49

7,915

10.0

300

208/230

10.20

7.61

9,510

28.0

460

11.80

8.80

11,000

14.6

575

10.20

7.61

9,510

13.0

BHP

Brake Horsepower

BkW

Brake Kilowatts

UNIT 580F

MOTOR EFFICIENCY

(%)

5 Hp

87.5

7.5 Hp

88.5

10 Hp

89.5