581a155-180 – Bryant 581C User Manual

Page 18

Advertising
background image

18

ARI* CAPACITY RATINGS — 581A155,180

LOW HEAT UNITS

HIGH HEAT UNITS

LEGEND

*Air Conditioning and Refrigeration Institute.
NOTES:

1. Rated in accordance with ARI Standards 360 and 270.
2. ARI ratings are net values, reflecting the effects of circulating fan

heat.

3. Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air tempera-
ture and 95 F db air entering outdoor unit.

IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.

4.

All 581A155, 180 units are in compliance with ASHRAE 90.1-
1999 Energy Standard for minimum EER requirements. Refer to
state and local codes or visit the following website: http://bcap-
energy.org to determine if compliance with this standard pertains
to a given geographical area of the United States.

HEATING CAPACITIES AND EFFICIENCIES — 581A155-180

*All units are 2-stage heat.
†Minimum heating cfm must be maintained to ensure proper heating operation.
NOTE: Minimum allowable temperature of mixed air entering the heat exchanger during first stage
heating is 45 F. There is no minimum mixed-air limitation during second-stage heating. For entering
air temperatures below 45 F, both stages of heat must be energized together to minimize conden-
sation issues and ensure proper unit operation. Mixed air below 35 F optional stainless steel heat
exchangers are recommended.

LOW OUTDOOR AIR TEMPERATURE

COOLING OPERATION LIMITS

AIR QUANTITY LIMITS (Cooling)

UNIT
581A

NOMINAL

TONS

NET COOLING

CAPACITY

(Btuh)

TOTAL

WATTS

EER

SOUND

RATING

(dB)

IPLV

155230

13

134,000

12,209

10.60

88

11.4

180275

15

180,000

17,064

10.50

88

11.4

UNIT
581A

NOMINAL

TONS

NET COOLING

CAPACITY

(Btuh)

TOTAL

WATTS

EER

SOUND

RATING

(dB)

IPLV

155300

13

134,000

12,218

10.60

88

11.4

180360

15

180,000

17,179

10.50

88

11.1

dB

Sound Levels (decibels)

db

Dry Bulb

EER — Energy Efficiency Ratio
IPLV — Integrated Part-Load Values
wb

Wet Bulb

UNIT 581A

HEATING

INPUT (Btuh)

Stage 2/Stage 1*

OUTPUT

CAPACITY

(Btuh)

TEMPERATURE

RISE (F)

AGA STEADY

STATE

EFFICIENCY (%)

MINIMUM HEATING

CFM†

155230

230,000/172,000

186,000

15-45

81.0

3750

155300

300,000/225,000

243,000

30-60

81.0

3830

180275

275,000/206,000

223,000

15-45

81.0

4580

180360

360,000/270,000

292,000

20-50

81.0

5400

UNIT SIZE

581A

TEMPERATURE LIMIT (F)

Standard

Unit

Unit With

Low Ambient Kit

Unit With

Motormaster®

Control

155, 180

40

20

–20

UNIT 581A

MINIMUM CFM

MAXIMUM CFM

155

3900

6500

180

4500

7500

Advertising