Class1 FoamLogix 2.1A & 1.7AHP REV D User Manual

Page 30

Advertising
background image

FoamLogix, Model 2.1A and 1.7AHP Class “A”

Electronic Foam Proportioning Systems

30

Foam suction connections

Tank drainage

Proper fill openings, per NFPA requirements.

In addition, a foam tank refill system may

be required. See Hale EZFill system for

installation requirements.

CONTROL UNIT AND INSTRUCTION/
SYSTEM DIAGRAM PLACARD

Determine a location on the operator panel of the

apparatus for the control unit and instruction/ system

diagram placard, if provided. These components

must be located at the main pump operator position

in close proximity to each other. Consideration

must be given for routing the control cable from the

control unit to the distribu tion box on the foam pump

and motor assembly. If necessary, order longer

or shorter cable as semblies to suit the location

demands.

INSTALLER SUPPLIED COMPONENTS

Due to the many differences in apparatus con-

figurations and design requirements the Hale

FoamLogix system installer must supply compo-

nents, such as,

mounting brackets

piping

hoses

fittings

electrical wiring

foam tank(s)

The following guidelines are recommendations for

selection of additional components for a complete

system installation. These recommen dations

reflect materials and components that are tested

extensively with Hale FoamLogix systems and

provide proven reliable performance.

Foam Concentrate Suction Hose

The Hale FoamLogix 2.1A and 1.7 AHP Foam

systems are provided with 15’ (4.6 meters) of 1/2”

(13mm) ID reinforced PVC foam concentrate suction

hose. The system installer may need to supply

additional fittings and hose from the foam tank to the

inlet of the foam pump.

All components selected transfer foam con centrate,

therefore they must be compatible with the foam

concentrates being used in the system. Hoses for

Class A foam concen trates have minimum 1/2”

(13mm) inside diameter.

Hoses for the foam concentrate suction must have

a rating of 23” (584 mm) Hg vacuum and 50 PSI

(3.5 BAR) pressure or greater.

Note: NFPA requires that foam concentrate suction

hose be clear to observe foam concentrate flow

during foam pump operation.

Recommended Components

Hose: PVC, Kuriyama Kuri-Tec K3130 or K7130

series

Fittings: Hose Barb Type; Brass, Stainless

Steel or Nylon

A tee with foam tank shut-off valve and a drain

valve is recommended in the foam tank suction

hose to allow, tank drainage and easier priming.

These components are subject to the same material

characteristics and pressure ratings as stated

above.

The foam concentrate strainer includes a shut-

off valve. This valve is used to shut off foam

concentrate flow to service the strainer.

Advertising
This manual is related to the following products: