FoamLogix, Model 2.1A and 1.7AHP Class “A”

Electronic Foam Proportioning Systems

66

SIMULATED FLOW OPERATION

The Simulated Flow mode of the Hale FoamLogix

system allows operation of the foam pump without

discharging water through a foam ca pable discharge

or when the flow sensor is not functioning.

The simulated flow mode is used for draining the

foam tank for:

Cleaning

Checking calibration of the feedback sensor

Verifying foam pump operation

Manually controlling foam injection if the flow

sensor malfunctions.

The factory default simulated flow rate is 150

GPM (568 LPM). The simulated flow rate and the

concentrate injection percentage rate are set by the

rate adjustment buttons on the control unit display,

while in simulated flow mode.

The simulated flow function provides manual

operation of the foam injection system required by

NFPA standards.

CAUTION!

WHEN OPERATING THE HALE FOAMLOGIX IN

SIMULATED FLOW MODE AN OUTLET FOR THE

FOAM CONCENTRATE MUST BE PROVIDED TO

PREVENT EXCESSIVE PRESSURE BUILDUP IN

DISCHARGE PIPING OR HOSES.

Simulated flow sequence

Uncoil and place the end of the bypass hose

1.

into a suitable container to collect the foam

concentrate.

Place the BYPASS valve in the

2.

BYPASS

position.

Energize the apparatus electrical system and

3.

press Hale FoamLogix power button (

i ) to turn

ON the system.

The Hale FoamLogix enters the STANDBY

4.

mode. (See Figure 41: “Display - Simu lated

Flow Operation.”)

Figure 41: Display - Simulated Flow Operation

64

FOAMLOGIX, Model 2.1A Class "A"

Electronic Foam Proportioning System

Operation

ISO 9001 CERTIFIED

The Simulated Flow mode of the Hale FoamLogix

system allows operation of the foam pump

without discharging water through a foam ca-

pable discharge or when the flow sensor is not

functioning.

The simulated flow mode is used for draining the

foam tank for:

Cleaning

Checking calibration of the feedback

sensor

Verifying foam pump operation

Manually controlling foam injection if the

flow sensor malfunctions.

The factory default simulated flow rate is 150

GPM (568 LPM). The simulated flow rate and

the concentrate injection percentage rate are set

by the rate adjustment buttons on the control unit

display, while in simulated flow mode.

The simulated flow function provides manual

operation of the foam injection system required

by NFPA standards.

CAUTION!

WHEN OPERATING THE HALE FOAMLOGIX IN

SIMULATED FLOW MODE AN OUTLET FOR THE

FOAM CONCENTRATE MUST BE PROVIDED TO

PREVENT EXCESSIVE PRESSURE BUILDUP IN

DISCHARGE PIPING OR HOSES.

Simulated flow sequence

1. Uncoil and place the end of the bypass

hose into a suitable container to collect the

foam concentrate.

2. Place the BYPASS valve in the

BYPASS

position.

3. Energize the apparatus electrical system

and press Hale FoamLogix power button

(

i ) to turn ON the system.

4. The Hale FoamLogix enters the STANDBY

mode. (See Figure 41: “Display - Simu-

lated Flow Operation.”)

SIMULATED FLOW OPERATION

Figure 41: Display - Simulated Flow Operation

Diaplay - Entering Simulated Flow Mode

Simultaneously

PRESS and RELEASE

Diaplay - Simulated Flow Mode