FoamLogix, Model 2.1A and 1.7AHP Class “A”

Electronic Foam Proportioning Systems

61

The value is in the same unit of measure as the

water flow. This totalized value may be reset - see

heading “Reset Function”.

For example, the display may show

9.5,

indicating 9.5 gallons (36 liters) of foam

concentrate have been used. (See Figure

37: “Display - Function Modes” on page 60.)

Bar Graph

The bar graph consists of a ten (10) LED array.

When the ON button is pressed the left-most LED

lights to indicate the system is ON and ready to

inject foam concentrate.

When water is flowing, LEDs to the right on the bar

graph light indicating foam concen trate is being

injected. The amount of LEDs lighted provides an

indication of the approxi mate pump capacity being

used.

If water flow requirements exceed the capac ity of

the pumps ability to deliver foam con centrate, pump

speed increases to the maxi mum rate. All bar graph

LEDs light and the right-most LED flashes, warning

the operator that the system capacity is being

exceeded and is running “lean” on foam concentrate

percentage.

If the flow decreases such that the required

injection rate is less than the lowest rating of the

pump, pump spped decreases to its minimum

rate and the first bar graph LED to the left flashes,

warning the operator that the system capacity

is being exceeded and is running “rich” on foam

concentrate percentage.

RESET FUNCTIONS

The totalized values for water and foam concen-

trate pumped are cleared from memory by

performing a

RESET function.

Using the DISPLAY button (

1

i), select either TOTAL

WATER or TOTAL FOAM.

By pressing and holding both the

2

and

buttons

at the same time, the value shown is cleared and the

display shows zero (0).

Additionally the totalized values for water and foam

3

concentrate reset to zero auto matically when the

apparatus power is turned OFF.

FOAM CONCENTRATE INJECTION RATE

When

% FOAM is selected, the  and  buttons

respectively increase or decrease foam concen trate

percentage.

While operating in any function, with the excep-

tion of

FLOW during simulated flow operation,

whenever the  or  buttons are momentarily

pressed, the display switches to the

% FOAM

display and shows the current injection rate for 2

seconds.

In any display mode, if either the  or  button

is held down for a period of 2 seconds or more,

the injection rate value increases or decreases

accordingly. Once released, the display returns to

the last selected display after 2 seconds.

When a reset is performed in the

% FOAM display

mode, the foam concentrate injection rate returns to

the default value.

WARNING MESSAGES

Several safety features are incorporated into

the Hale FoamLogix system to protect the foam

concentrate pump, electric motor and apparatus

wiring while maintaining personnel safety.

Messages appearing on the display alert the