FoamLogix, Model 2.1A and 1.7AHP Class “A”

Electronic Foam Proportioning Systems

70

o Drain the fire pump, valves and fire pump

system accessories.

The foam system is now winterized and ready

for cold weather duty transport and/or cold

weather storage.

After transport, prior to the placing the unit in

service:

• Drain the foam concentrate reservoir of anti-

freeze in an environmentally friendly fashion.

• Shut all foam reservoir drain valves.

• Fill the foam reservoir with a Hale approved

compatible Class A foam concentrate.

• Establish a water supply to the fire pump and

install a discharge hose and nozzle.

• Operate the fire pump and discharge 100-

gpm (380 LPM) of water from a foam capable

apparatus discharge. Be sure to collect the

discharge in an area, to be cleaned-up later,

to mitigate any environmental impact that the

anti-freeze / foam solution may cause.

• Turn the foam system “on.”

• Depress the “up” arrow and raise the foam

injection rate to 3.0%.

• Operate the discharge hose for one minute.

• Shut the foam system “off.” Turn the fire

pump “off.” Remove the hose and nozzle.

Disconnect the water supply.

• The unit is now ready for service.