FoamLogix, Model 2.1A and 1.7AHP Class “A”

Electronic Foam Proportioning Systems

31

Foam Concentrate Discharge Hose

The system installer must supply fittings and hoses

from the foam pump inject connection to the check

valve/injector fitting inlet. All components selected

transfer foam concen trate, therefore they must be

compatible with the foam concentrates being used

in the system.

The foam pump discharge connection is a 1/2” (13

mm) compression fitting. The check valve injector

fitting connection has 1/2” NPT threads. Hoses and

fittings of 1/2” minimum diameter rated at 500 PSI

(34.5 BAR) work ing pressure or maximum discharge

pressure of the fire pump must be used. Fittings and

hoses must be compatible with all foam agents to be

used.

Recommended Components

Hose: Aeroquip 2580-8 or Equivalent

Reinforced Hydraulic Hose.

Fittings: Brass or Stainless Steel Hose End

Crimp or Reusable Type (Aeroquip 412-9-8 or

Equivalent)

Foam Concentrate Bypass Hose

The foam concentrate bypass hose connec tion is

a 1/2” (13mm) hose barb connection. Hoses and

fittings of nominal 1/2” diameter must be used as

bypass hose. Since the bypass hose is used for

calibration and draining the system it does not see

high operating pressures; therefore, a hose with a

lower pressure rating than the inject hose may be

used.

Fittings and hoses used must be compatible

with all foam agents expected to be used. Use

fittings made of brass or 300 series stainless steel

compatible with all foam concentrates.

Recommended Components

Hose: Low Pressure Hydraulic Hose or Air

Brake Tubing

Fittings: Brass or Stainless Steel

It is recommended that the foam concentrate

bypass hose be long enough to extend past the

apparatus running board to reach five (5) gallon

(19 liter) containers, making foam pump setup and

calibration simpler.

Check Valves

Check valves must be installed on the appa ratus

with foam systems to prevent contami nation of the

foam concentrate with water and contamination

of the fresh water tank with foam. (See Figure 3:

“Typical Hale Foam-Logix 2.1A and 1.7AHP System

Layout” on page 21.)

When a Hale FoamLogix 2.1A and 1.7AHP foam

injection systems and related components are

properly installed the required check valves are

integral parts of the system.

NFPA standards require a check valve in the foam

concentrate injection line at the injection point. The

Hale p/n: 038-1790-00-0 Integral Check Valve/

Injector Fitting, a standard component included with

the Hale FoamLogix 2.1A and 1.7AHP systems and

installed when a manifold kit is ordered, meets these

requirements and threads directly into the foam

injection port on Hale manifolds.

Check valves must be installed in all water piping

locations where foam concentrate could drain

back into pumps or other compo nents of the fire

apparatus.

As a minimum one check valve must be installed

where the water piping that supplies foam solution

connects to the fire pump discharge. To more

effectively keep foam contamination out of the fire

pump and water tank, double check valves are

recommended.