Flow sensor calibration – Class1 FoamLogix 2.1A & 1.7AHP REV D User Manual

Page 54

Advertising
background image

FoamLogix, Model 2.1A and 1.7AHP Class “A”

Electronic Foam Proportioning Systems

54

52

FOAMLOGIX, Model 2.1A Class "A"

Electronic Foam Proportioning System

Installation

ISO 9001 CERTIFIED

FLOW SENSOR CALIBRATION

Verify flow sensor calibration during NFPA/UL

testing of the apparatus and delivery to end user.

IMPORTANT!

AN ACCURATE FLOW MEASURING DEVICE MUST

BE USED TO MEASURE THE WATER FLOW WHEN

CALIBRATING THE FLOW SENSOR. USE A

SUITABLE SIZE, SMOOTH BORE, NOZZLE AND AN

ACCURATE AND CALIBRATED PITOT GAUGE

INSTRUMENT. HAND HELD PITOT GAUGES ARE

USUALLY NOT VERY ACCURATE.

MAKE SURE THE SYSTEM IS CALIBRATED WITH

AN ACCURATE FLOW MEASURING DEVICE.

1. Determine the water flow normally ex-

pected from the discharge outlet and

establish flow.

2. Make sure the water flow established is

within the range of the flow sensor moni-

toring the discharge.

For example, establish a flow rate of 150

GPM (568 LPM) of water through a nozzle

and Pitot system. Compare the calculated

flow value to the value shown on the

control unit display.

Figure 26: Display - Password and Calibration Modes

SELECT DISPLAY

Press and

HOLD

Continued to

HOLD

Displayed when

 is pressed

Pressed in

sequence to

enter passwords

Displayed when

is pressed

Release when

CAL is shown

Figure 27: Display - Flow Sensor Calibration

Figure 26: Display - Password and Calibration Modes

52

FOAMLOGIX, Model 2.1A Class "A"

Electronic Foam Proportioning System

Installation

ISO 9001 CERTIFIED

FLOW SENSOR CALIBRATION

Verify flow sensor calibration during NFPA/UL

testing of the apparatus and delivery to end user.

IMPORTANT!

AN ACCURATE FLOW MEASURING DEVICE MUST

BE USED TO MEASURE THE WATER FLOW WHEN

CALIBRATING THE FLOW SENSOR. USE A

SUITABLE SIZE, SMOOTH BORE, NOZZLE AND AN

ACCURATE AND CALIBRATED PITOT GAUGE

INSTRUMENT. HAND HELD PITOT GAUGES ARE

USUALLY NOT VERY ACCURATE.

MAKE SURE THE SYSTEM IS CALIBRATED WITH

AN ACCURATE FLOW MEASURING DEVICE.

1. Determine the water flow normally ex-

pected from the discharge outlet and

establish flow.

2. Make sure the water flow established is

within the range of the flow sensor moni-

toring the discharge.

For example, establish a flow rate of 150

GPM (568 LPM) of water through a nozzle

and Pitot system. Compare the calculated

flow value to the value shown on the

control unit display.

Figure 26: Display - Password and Calibration Modes

SELECT DISPLAY

Press and

HOLD

Continued to

HOLD

Displayed when

 is pressed

Pressed in

sequence to

enter passwords

Displayed when

is pressed

Release when

CAL is shown

Figure 27: Display - Flow Sensor Calibration

27: Display - Flow Sensor Calibration

FLOW SENSOR CALIBRATION

Verify flow sensor calibration during NFPA/UL testing

of the apparatus and delivery to end user.

IMPORTANT!

AN ACCURATE FLOW MEASURING DEVICE MUST

BE USED TO MEASURE THE WATER FLOW WHEN

CALIBRATING THE FLOW SENSOR. USE A SUITABLE

SIZE, SMOOTH BORE, NOZZLE AND AN ACCURATE

AND CALIBRATED PITOT GAUGE INSTRUMENT.

HAND HELD PITOT GAUGES ARE USUALLY NOT

VERY ACCURATE.

MAKE SURE THE SYSTEM IS CALIBRATED WITH AN

ACCURATE FLOW MEASURING DEVICE.

Determine the water flow normally ex pected

1.

from the discharge outlet and establish flow.

Make sure the water flow established is within

2.

the range of the flow sensor moni toring the

discharge.

For example, establish a flow rate of 150 GPM

(568 LPM) of water through a nozzle and Pitot

system. Compare the calculated flow value to

the value shown on the control unit display.