Class1 FoamLogix 2.1A & 1.7AHP REV D User Manual

Page 38

Advertising
background image

FoamLogix, Model 2.1A and 1.7AHP Class “A”

Electronic Foam Proportioning Systems

38

Using double check valves, separated by at least

6” to 8” (152 to 203mm) of pipe before the foam

injection point, ensures that the pump and tank

water remain uncontaminated.

Flow Sensor

The Hale FoamLogix flow sensor is specially

designed to enable quick and easy sensor

inspection and maintenance. The flow sensor paddle

wheel is installed on a saddle clamp or weld fitting to

the foam-capable discharge piping of the apparatus.

In horizontal piping runs, the flow sensor is mounted

within the range shown in Figure 12: “Flow Sensor

Tee Position Range.”

When selecting a flow sensor, it is important

to consider the minimum and maximum flow

requirements during operation. Refer to the Figure

4: “Pipe Size vs. Flow Rate,” on page 24, for the

proper pipe size for flow range desired.

The flow sensor is installed in the piping before the

foam concentrate injection point.

This is true in applications where the foam system

needs to supply a 3” (76mm) deck gun, as well as

a 1” (25.4mm) booster line.

Table 13: Pipe Size vz. Minimum Straight Run

Pipe size for flow sensor mounting must be

selected to provide accuracy at the lowest flow rate.

Mounting the flow sensor in a short section of pipe,

one pipe size smaller (e.g., 4” to 3”; 3” to 2-1/2”,

etc.), provides better accuracy at the lower flows.

Refer to the Table 13: “Pipe Size vs. Minimum

Straight Run” for pipe size. Selecting the next

smaller pipe permits reducing the straight pipe

run the required distance prior to the flow sensor

paddle wheel.

In the short length of reduced pipe pressure loss

is minimal and there is minimal pressure loss

through elbows and fittings. See Figure 14: “Typical

Reduced Size Sensor Piping Arrangement” on

page 39.

Excessive turbulence in the flow sensor may

produce unstable and inaccurate flow read ings.

The length of straight pipe prior to the flow sensor

must be sufficient to reduce any turbulence in the

pipe.

The following guidelines help attain the best

readings, and maintain Hale FoamLogix system

accuracy.

1. A minimum of

6 times the pipe diameter

of straight run pipe without any fittings is

necessary prior to the flow sensor paddle

wheel. (See Figure 15: “Flow Sensor

Placement” on page 39.)

Pipe Size

Minimun Recommend-

ed Straight Run Pipe

1-1/2”

9”

2”

12”

2-1/2”

15”

3”

18”

4”

24”

Advertising
This manual is related to the following products: