FoamLogix, Model 2.1A and 1.7AHP Class “A”

Electronic Foam Proportioning Systems

74

72

FOAMLOGIX, Model 2.1A Class "A"

Electronic Foam Proportioning System

Troubleshooting

ISO 9001 CERTIFIED

TROUBLESHOOTING CHARTS

Chart 44: Hale FoamLogix System Troubleshooting Flow Diagram

NO

Is Display Lit?

Is Power Available at

Connector C5?

PROVIDE

POWER

Remove C1 from

display. Check for

power at Term/ 1.

Is Power Available?

REPLACE

HARNESS

1

NO

YES

YES

NO

Establish Water Flow

YES

Replace Display

Is Water Flow Value

Displayed?

NO

Is Foam Discharge

OPEN?

OPEN FOAM

DISCHARGE

NO

YES

YES

Check Harness

Connection

OK?

RECONNECT

OR REPLACE

HARNESS

NO

YES

NO

Press ON Button.

Does Motor Run?

NO

Check LEDs on

Controller Box

YES

Verify Water Flow

Sensor Operative.

Is Sensor operating

correctly?

YES

RECONNECT

WATER FLOW

SENSOR

NO

Continued -

See

1 on

next Page.

Is Foam Concentrate

being Injected?

YES

Figure 44: Hale FoamLogix System Troubleshooting Flow Diagram