Class1 FoamLogix 2.1A & 1.7AHP REV D User Manual

Page 32

Advertising
background image

FoamLogix, Model 2.1A and 1.7AHP Class “A”

Electronic Foam Proportioning Systems

32

Separate two check valves by at least 6” to 8” (152

to 203mm) of piping to form a dead zone between

the check valves. Individual drain lines should be

used on each check valve. The waterway check

valves must be rated for 500 PSIG (34.5 BAR) test

pressure.

Flushing Water Hose

If a Hale and USFS approved Class “A” foam

concentrate is used, flushing of the Hale FoamLogix

2.1A and 1.7AHP systems is not necessary as long

as the system is used periodically.

If a flushing water hose is required to flush the

foam pump, it must have a pressure reducer/

regulator that limits the flush water pressure to

25 to 50 PSI (2 to 4 BAR). The tubing and fittings

used must be compatible with foam concentrates

being used in the system.

To be NFPA compliant, when flushing is required,

the system installer must provide proper

hoses

shut-off valves

check valves

reducer/regulator

connections for flushing water for the system.

Foam Discharge Drains

Drains must be provided from foam capable

discharge piping components to prevent freezing

in cold weather. When designing the drain system

care must be taken to prevent contamination of the

water system with foam and the foam concentrate

with water. Some multiple drain systems that allow

individual drain lines to communicate also allow

foam to bypass the installed check valves causing

contamination of fire pump and the water or foam

concentrate storage tanks.

Hale offers an optional manual or air-oper ated 6-port

drain valve, Class1 Model MMD6 (p/n: 104961). The

valve provides individual drains with a single control

and is use for applications where a single point for

multiple drains is required. If a Hale MMD6 drain

valve is not used, individual drain lines and valves

for foam capable discharge piping is recommended.

Apparatus design/build for cold weather

(below freezing) duty

If the end-user will use the fire apparatus in sub-

freezing temperatures, the onus is on the fire

truck builder to build into the apparatus design

an appropriate ambient temperature operating

environment for the envelope where the FoamLogix

system will be located. This routinely takes on

the form and function of mounting the FoamLogix

system in a limited ventilation area that is served

by an appropriate pump house auxiliary heater.

Simply, the fire truck builder must keep ambient air

temperature above 32

o

F (0 deg C) in the envelope

around the FoamLogix hardware, including the base

foam pump unit, foam strainer, foam concentrate

injection line, etc. There are several best practices

in the fire industry that can be employed to meet

this criteria and the fire truck builder/designer can

choose the best choice for their specific installation.

Note that there must be ventilation available to cool

the area around the unit also, to prevent electric

motor overheating when the unit is operating in high

temperature ambient environments.

Electrical Requirements

The system installer must provide the primary power

wire and a ground strap for the Hale FoamLogix

system.

Primary power must be supplied from the main

apparatus battery to the motor controller box on

the foam pump and motor assembly. The Hale

FoamLogix 2.1A and 1.7AHP require minimum 40

AMP electrical service.

Primary electrical power must be supplied directly

from the battery or the battery master disconnect

switch or solenoids to the Hale FoamLogix.

IMPORTANT!

OTHER ELECTRICAL COMPONENTS MUST NOT BE

SUPPLIED FROM THIS WIRE. DO NOT CON NECT

THE PRIMER AND HALE FOAMLOGIX TO THE SAME

POWER WIRE.

The primary power connection must be made so

Advertising
This manual is related to the following products: