FoamLogix, Model 2.1A and 1.7AHP Class “A”

Electronic Foam Proportioning Systems

69

SECTION 5 MAINTENANCE

MAINTENANCE PROCEDURES

After each use

1.

Inspect wiring, hoses, flow sensors and

connections for tightness, corrosion, leaks and.

or damage. Refer to Figure 3 on page 21.

Flush foam pump if a non-approved foam

concentrate is used. Also see appendix A, “Hale

Foam concentrate Compatibility” beginning on

page 87 for recommended foam concentrates.

Monthly

2.

Remove and clean the foam strainer screen.

Flush as required.

Monthly

3.

Verify water flow calibration.

Annually

4.

Verify foam feedback calibration.

Every two (2) months

5.

If an approved foam concentrate has been left in

the system, operate foam system to remove the

foam concentrate and prevent jelling.

FREEZE PROTECTION

Cold weather transport and cold weather storage of

FoamLogix systems:

• When transporting the completed fire

apparatus from the OEM to the dealer, and

the dealer to the end-user, or, when the end-

user decides to store the finished apparatus

in an unheated area subject to below freezing

temperatures, a FoamLogix winterization

process must be used.

• Any water and/or foam concentrate that

is in the foam concentrate reservoir, foam

concentrate pump, and associated foam

system piping/tubing will freeze and then

break system components when the system

is subjected to subfreezing temperatures

commonly found in over-the-road driving

during fire truck delivery and transport. The

following precautions must also be taken

by OEMs, end-users, re-sellers, fire truck

dealers, transport agencies, etc., that will be

transporting and/or storing the apparatus in

below freezing temperatures:

o Drain the foam concentrate storage

reservoir in accordance with safe foam

concentrate handling practices as outlined

by the foam concentrate manufacturer. If

the foam reservoir is filled with only water,

completely drain the storage compartment

of water. After empty, close all drain valves.

o Pour in five gallons (18.93L) of an

appropriate antifreeze solution in the foam

concentrate reservoir. Consider using an

environmentally friendly biodegradable

formulation.

o Follow the Installation and operation manual

procedure to “prime” the foam pump.

o With the apparatus fire pump in gear, a

water supply established, and a discharge

hose and nozzle attached to the discharge

side of the fire pump, discharge over

100-gpm (380 LPM)from a foam capable

discharge.

o Turn the FoamLogix system “on.” Depress

the “up” arrow and raise the proportioning

rate to 3.0%.

o Continue to discharge water out of the

discharge hose for one-minute.

o Shut the FoamLogix system “Off.”

o Shut off the discharge valve and shut the

fire pump down. Remove the water supply

connection to the fire pump.