2 transmitter output definitions, 2 transmitter output definitions -2, Figure 44 transmitter output terminals -2 – CiDRA GVF-100 Gas Volume Fraction Monitoring System User Manual

Page 53

Advertising
background image

Copyright © 2006 CiDRA Corporation

Page 9-2

20639-01 Rev 03

9.2

Transmitter Output Definitions

The following figure shows a diagram of the output portion of the
terminal board. The outputs of the transmitter are connected to
communicate between the transmitter and other equipment.

Figure 44

Transmitter Output Terminals

COMM

– This denotes the connection point for serial digital

communications. Either RS232 or RS485 communications is
supported with baud rates settable between 2400 and 115200 baud (8
bits, no parity, 1 stop bit). The communications type (RS232/485) as
well as the baud rate can be set by the front panel keypad as listed in
a later section of the manual.

Note:

If intermittent RS-485 communication problems are observed, it

may be necessary to put bus terminations of 120 ohms at the extreme
ends of the bus between COM+ and COM-. Should this be
necessary, follow best practices in selecting the resistor and in
connecting it reliably to the bus. However, it is a violation of Class I
Division 2 rating of the SONARtrac

TM

transmitter to install the bus

termination resistor physically within this enclosure. A different
Class I Division 2 enclosure must be used to house the bus
termination resistor if the SONARtrac

TM

transmitter is installed in

a Class I Division 2 location.

Advertising