Externally Powered 4-20mA Loop Configuration

- The hookup for a

4-20mA interface configured as “Externally Powered” is shown below.
The maximum value of V

EXT

should be chosen such that the maximum

applied voltage between V

EXT

and local ground and I

OUT

and local

ground shall be within the range of +30V / -10V and current limited to
100mA. The maximum value of R

L

is determined by the following

equation:

R

L Max

= (V

EXT

– 8.35) / (0.022)

For example, with V

EXT

= 24VDC:

R

L Max

= (24-8.35) / (0.022) = 711 Ohms

In the externally powered configuration the 4-20mA interface is
capacitively isolated from the rest of the transmitter electronics
provided that the applied voltages are within +30V / -30V.

Figure 48

Externally Powered 4–20mA Loop

SHD

- The three SHD (shield) terminals should only be used for

grounding shields of any output wiring such as connections to CUR 1
or CUR2. These should not be used for the SENSOR 1 or 2 shields
nor for the Sensor Head To Transmitter cable shield. Only one end of
the shield wire should be connected to eliminate shield currents.

Plant Control System

R

L

+

-

V

EXT

SONARtrac

TM

Transmitter

4-20mA