CiDRA GVF-100 Gas Volume Fraction Monitoring System User Manual

Page 68

Advertising
background image

Copyright © 2006 CiDRA Corporation

Page 9-17

20639-01 Rev 03

Level 1

Level 2

Level 3

Range

Description

Output Sel

SOS, GVF, Blank

Parameter to output

Power Sel

Internal, External

Power supply for 4-
20mA current

Low End

Based on ‘output sel’

Low end output (4mA)

High End

Based on ‘output sel’

High end output (20mA)

Out of Range

Hold, >20mA, <4mA,
4mA

Behavior when meter
reading is out of range
or meter has no reading

Overrange
Rail

Enable, Disable

‘Enable’ causes the
output to go to full
(20mA) or min (4mA)
when system over
ranges

4mA Trim

2 to 6

Adjust 4mA output

4-20mA
Ch1& Ch2

20mA Trim

18 to 22

Adjust 20mA output

Multiplier

0 - 999999

Multiplier on output

Width (ms)

.5,1,20,33,50,100

Pulse width

Lowcut

0 % to 100 %

Low end cutoff

Pulse

Output Sel

GVF, SOS

Parameter to output

Warning Off/On

Activates alarm warning
function

Critical

0 % to 100 % Off/On

Activates alarm critical
function

Alarm
Control

Manual Clear Off/On

Allows for manual or
automatic alarm
clearing

GVF Min

Alarm
Warning
Threshold

GVF Max

0-100% of range

Used to set the
minimum and maximum
values for a warning
alarm

GVF Min

Alarm Critical
Threshold

GVF Max

0-100% of range

Used to set the
minimum and maximum
values for a critical
alarm

State

Enable, Disable

Enable Damping

GVF
Damping

Time
Constant (s)

0-600 seconds; default
is 3

Smoothes output due to
rapid changes in flow

State Enable,

Disable Enable noise filtering

GVF Noise
Filter

Magnitude

Low, High

Amount of damping

State Enable,

Disable Enable spike filtering

Length

2 - 60 readings

# of measurements to
validate

Output Config

GVF Spike
Filter

Delta

0 – 100 %

% of full measurement
range that will define
the spike size to be
rejected