CiDRA GVF-100 Gas Volume Fraction Monitoring System User Manual

Page 54

Advertising
background image

Copyright © 2006 CiDRA Corporation

Page 9-3

20639-01 Rev 03

PULSE

– An isolated solid-state switch-closure-type output occurs

between P+ and P- whenever conditions are met that are determined
by the pulse setting within the transmitter. The maximum applied
voltage between P+ and local ground and P- and local ground shall be
within the range of +30V / -10V. The load current shall be a maximum
of 100mA. Typical turn on time is 1 msec. Typical turn off time is 0.1
msec.

Figure 45

Pulse Switch Closure

For sizing R

1

refer to the following example.

Power Supply = 24V

Choose a value for R

1

so as to not exceed 100mA

R

1

= 24V / 100mA = 240

Therefore, R

1

should be sized to be greater than

240

Ω so the current does not exceed 100mA

ALARM

– An electrically isolated switch closure occurs between AL+

and AL- whenever the limits specified in the transmitter setup for
Alarm are met. These limits can be changed or disabled through the
local keypad and display. The maximum applied voltage between
AL+ and local ground and AL- and local ground shall be within the
range of +30V / -10V. The load current shall be a maximum of
100mA.

Figure 46

Alarm Switch Closure

AL+ (HI)

AL- (LOW)

Solid-State
Relay Closure

Transmitter
Terminal Board

+ Out

- Out

R

1

Power
Supply

P+

P-

To Counter
Inputs

+

-