4.7.2.1.a

Three-Phase Direct-to-Mains Connection Topology

Figure 9: Non-Isolated Three-Phase Connection Topology

Caution:

Do not connect VN- to PE. In a direct-to-mains connection the VN- must

not be connected to the PE, as this will cause irreparable damage to the
system.

Take care and note that in a direct-to-mains connection the Neutral point is

not the most negative voltage level. It is the mid-point level of the rectified
DC bus.