B single-phase direct-to-mains connection topology – ElmoMC Gold Line Digital Servo Drives-Gold Trombone User Manual

Page 45

Advertising
background image

Gold Trombone Installation Guide (EtherCAT and CAN)

Installation

MAN-G-TROIG-EC (Ver. 1.604)

www.elmomc.com

45

4.7.2.1.b

Single-Phase Direct-to-Mains Connection Topology

Figure 10: Non-Isolated Single-Phase Connection Topology

The Power Supply is connected directly to the mains AC line.

Warning:

Do not connect VN- to PE. In a direct-to-mains connection the VN- must

not be connected to the PE, as this will cause irreparable damage to the
system.

Take care and note that in a direct-to-mains connection the Neutral point is

not the most negative voltage level. It is the mid-point level of the rectified
DC bus.

Advertising