Chapter 5: installation, Hardware requirements, Ac input requirements – ElmoMC Gold Line Digital Servo Drives-Gold Tuba User Manual
Page 11: Recommended wire cross-sections (all models), Chapter 5, Installation
Advertising
![background image](/manuals/558355/11/background.png)
Gold Tuba Installation Guide
MAN-G-TUBIG-EC (Ver. 1.201)
|Hardware Requirements
11
Chapter 5:
Installation
The Gold Tuba must be installed in a suitable environment and properly connected to its voltage
supplies and the motor.
5.1. Hardware Requirements
AC Input Requirements
Circuit Breakers & Contacts
Three-Phase Supply Voltage
Circuit breaker current rating
40 A Type C
Circuit breaker voltage rating
250 VAC / 480 VAC depending upon operating
AC voltage
Contactor
40 A
Recommended Wire Cross-Sections (All Models)
Feature
Connection
Details
Recommended Maximum Wire Gauge
30 A Model
40 A Model
AC input
AC1, AC2, AC3
14 AWG
12 AWG
Protective Earth
PE
14 AWG
12 AWG
Note:
The actual size is determined by the drive’s current model.