2 brief description, Brief description – EUCHNER AS-i Safety Monitor for 2 AS-i circuits User Manual

Page 11

Advertising
background image

AS-i Safety Monitor for 2 AS-i circuits

General

Subject to reasonable modifications due to technical advances

Id.-No.: 103336

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

11

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

2.2

Brief description

The Actuator-Sensor-Interface (AS-i) has been established as a system for net-
working primarily binary sensors and actuators on the lowest level of the automa-
tion hierarchy. The large number of installed systems, ease of use and reliable
operating behavior make AS-i also ideal for machine safety applications.

The safe AS-i system is intended for safety applications up to Category 4/SIL 3.
Mixed use of standard components and safety components is possible.

The AS-i Safety Monitor performs monitoring within an AS-i system of the user-
assigned safety slaves based on the configuration the user has set using configu-
ration software. In case of a Stop request or a fault condition, the AS-i Safety
Monitor safety shuts off the system with a response time of maximum 40 ms.

Abb. 2-1. Safety configured and standard components in an AS-i network

Multiple Safety Monitors can be used within one AS-i system. A safe slave can be
monitored by more than one AS-i Safety Monitor.

AS-i Gateway

AS-i power supply

Safety light grid

Safety
light grid

Standard

module

Safety

E-STOP switch

Safety

module

Safety
limit switch

Standard-

Modul

AS-i Safety monitor