Spezifications, 1 technical data, 1 data sheet 103303 – EUCHNER AS-i Safety Monitor for 2 AS-i circuits User Manual

Page 16: Technical data, Data sheet 103303, As-i safety monitor for 2 as-i circuits

Advertising
background image

16

Subject to reasonable modifications due to technical advances

Id.-No.: 103336

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

AS-i Safety Monitor for 2 AS-i circuits

Spezifications

4.

Spezifications

4.1

Technical data

4.1.1

Data sheet 103303

Attention!

The AS-I power supply for the AS-I components must have isolation per IEC 60
742 and be able to handle momentary power interruptions of up to 20 ms. The
power supply for the 24 V supply must also have isolation per IEC 60 742 and be
able to handle momentary power interruptions of up to 20 ms. The maximum out-
put voltage of the power supply must also be less than 42 V in case of a fault.

103303

Safety monitor

advanced monitor

Release circuit

4-channel

Start delay

< 10 s

Respond delay

< 40 ms

Baud rate

19,2 kBaud, no parity, 1 start bit, 1 stop bit, 8 data bits

Inputs:
4 x EDM/Start

EDM: inputs of external device monitoring circuits
Start: start inputs
switching current statical 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 µs)

Outputs:
4 x output switching elements

relay outputs (output circuits 1 and 2)
max. contact load: 3 A AC-15 at 30 V, 3 A DC-13 at 30 V

semiconductor outputs (output circuits 3 and 4)
max. contact load: 0,5 A DC-13 at 30 V

Interface

RS 232, chip card slot

Displays

LCD

indication of slave addresses and error messages

LED power

AS-i voltage OK

LED fault

LED on: communication error on AS-i network
LED flashing: at least 1 OSSD in state „red flashing“

LED ready

LED on: start-up/restart-disable active
LED flashing: external test necessary

LEDs U AS-i 1 / U AS-i 2

AS-i 1/AS-i 2 sufficiently voltage supplied

LED AUX

auxiliary power

4 x LEDs EDM/Start

state of input of ext. device monitoring circuit:
LED off:

open

LED on:

closed

4 x LEDs output circuits

state of output circuits:
LED off:

open

LED on:

closed

Advertising