AS-i Safety Monitor for 2 AS-i circuits

Diagnostics for AS-i Monitor and networking using AS-i Master

Finally following in channel 3 is the collective information for the colors of the de-
vices in the release circuits.

Then the individual information is listed.

Channels 1 and 2 describe the states of the respective release circuits (OSSD’s)
of the Safety Monitor. For status codes and colors see section <Status codes for
the release circuits (OSSD)>.

Channel 3 contains information as to whether there are warnings or faults in a re-
lease circuit for one or more of the devices associated with this release circuit.
The information is as follows:

EF

Ground fault

There is a ground fault
1: There is a ground fault
0: There is not a ground fault

DA

Duplicate
address

There is a duplicate address
1: Duplicate address on AS-i
0: No duplicate address on AS-i

GN

Green

Errorless or nearly errorless communication
Less than 1% telegram repetitions on AS-i

YE

Warning

More frequent repetitions which need to be clarified depend-
ing on the application
1% - 5% telegram repetitions on AS-i

RD

Fault

Serious faults
Over 5% telegram repetitions on AS-i

UA

UAS-i

The AS-i voltage is sufficient
1: Voltage is sufficient
0: Voltage is not sufficient

AU

AUX 24 V

The 24 V for supplying the safe outputs is present
1: 24 V for supplying the safe outputs is present
0: 24 V for supplying the safe outputs is not present

Tab. 11-7.

YF

Yellow flashing

At least one of the devices associated with this release cir-
cuit is in the yellow flashing state

RF

Red flashing

At least one of the devices associated with this release cir-
cuit is in the red flashing state

Tab. 11-8.