Coupling slave – EUCHNER AS-i Safety Monitor for 2 AS-i circuits User Manual

Page 56

Advertising
background image

56

Subject to reasonable modifications due to technical advances

Id.-No.: 103336

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

AS-i Safety Monitor for 2 AS-i circuits

Operation in advanced display mode

Confirm with OK (display flashes)

Use the arrow keys to enter the desired address

Confirm with OK (display stops flashing)

Use one of the two arrow keys to exit the input screen

Save with OK, or cancel the process by pressing ESC.

The teaching procedure was successful if an OK appears in the third line.

The following error messages are possible:

Press the OK key to save the learned code table or press ESC to discard it.

9.3.1.3

COUPLING SLAVE

Main Menu || AS-I SAFETY || TEACH CODES || COUPLING SLAVE ||

This menu point allows you to teach the code table for a coupling slave. To con-
tinue, enter the PIN and confirm with OK.

In the following menu you select the AS-i circuit.

After selecting the AS-i circuit the safe unit switches to configuration mode.

Then enter the slave address.

Information!

Be sure that all slave contacts on the corresponding slave are closed.

Message Description

RR

Both contacts open

RX

Left contact open, right contact closed.

XR

Right contact open, left contact closed.

TEACH CODES
ENTER PIN
0000
OK

AS-I CIRCUIT 1
AS-i CIRCUIT 2

COUPLING SLAVE
SLAVE ADDR.

––1

ESC