3 acyclical data, Status codes for the release circuits (ossd), Transparent output data – EUCHNER AS-i Safety Monitor for 2 AS-i circuits User Manual

Page 83: Acyclical data, Code bit [3 ] status / color description, Bit lamp color

Advertising
background image

AS-i Safety Monitor for 2 AS-i circuits

Diagnostics for AS-i Monitor and networking using AS-i Master

Subject to reasonable modifications due to technical advances

Id.-No.: 103336

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

83

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

11.4.2.1

Status codes for the release circuits (OSSD)

11.4.2.2

Transparent output data

The transparent output data are available there to the safe unit as non-safe addi-
tional bits, for example for Start keys.

11.4.3

Acyclical data

Vendor Specific Object 1 – Analyzer status AS-i Circuit 1

Read only.

This object contains a bit pair for all 62 possible slaves which represents the sta-
tus of the slaves at this address:

Information!

Monitors supporting less than 8 release circuits set all non-present release circuits to
“gray”.

Code bit [3..0]

Status / color

Description

0

continuous green

Output on

1

flashing green

Wait time for Stop 1 in effect

2

continuous yellow

Startup / restart active

3

flashing yellow

External test required / acknowledgement /
Turn-on delay active

4

continuous red

Output off

5

flashing red

Fault

6

gray or off

Output not assigned

7 ... F

reserved

Tab. 11-9.

Ch

2

15

2

14

2

13

2

12

2

11

2

10

2

9

2

8

2

7

2

6

2

5

2

4

2

3

2

2

2

1

2

0

0

reserved

Start2

EDM 2 Start1

EDM 1

Tab. 11-10.

Bit

Lamp color

11

red

10

yellow

01

green

00

no slave

Tab. 11-11.

Advertising