Lenze · I/O system 1000 · commissioning guidelines for the PLC Designer · DMS 1.2 EN · 11/2012 · TD05

27

4

Mapping the real station structure in the »PLC Designer«

4.4

Configuring I/O modules on the CANopen bus coupler module

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Add the PDO configuration for the counter discs.
The following example uses a send PDO and a mapping element to describe the basic

configuration process.

• Proceed accordingly when configuring the transmit PDOs (Send PDO Mapping tab).

6. Click the "EPM_S110" device in the device view S110to open its settings.
7. Click Add PDO... on the Receive PDO Mapping to add receive PDOs.

• Depending on the counter discs used, one or several PDOs must be added in send and

receive direction.

• Please refer to the module documentation to see which additional elements of the

process image of the counter modules are required for operation.

8. Select added PDOs and click Add Mapping....

• Select the corresponding settings in the dialog box that appears.

Note!

If Autoconfig. PDO Mapping (see step 3) is reactivated after adding the manual

configuration, the entire configuration that has been added manually will be deleted.