2 epm_s202: digital inputs, 3 epm_s303: digital outputs, 4 epm_s400: analog inputs – Lenze E70ACxS Application Sample i700 (PLC Designer v3) User Manual

Page 17: Epm_s202: digital inputs, Epm_s303: digital outputs, Epm_s400: analog inputs, Overview - the structure of the application sample

Advertising
background image

Lenze · Servo Inverter i700 | Application Sample · DMS 1.0 EN - 09/2012 - TD11

17

Overview - The structure of the Application Sample

A90_Resources

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.4.2

EPM_S202: Digital inputs

The hardware configuration of the sample project contains eight digital inputs. The corresponding

Lenze Teachware case i700 contains a control panel for controlling the inputs of the I/O system.

• Digital input 1: Mapped to the global variable for quick stop (QSP).
• Digital input 3: Mapped to the global variable of the negative hardware limit switch for AxisZ.
• Digital input 4: Mapped to the global variable of the positive hardware limit switch for AxisZ.

5.4.3

EPM_S303: Digital outputs

The hardware configuration of the sample project contains eight digital outputs. The corresponding

Lenze Teachware case i700 contains a control panel for evaluating the outputs of the I/O system.

• Global variable DriveReadyX is mapped to digital output 1.
• Global variable DriveReadyY is mapped to digital output 2.
• Global variable DriveReadyZ is mapped to digital output 3.

5.4.4

EPM_S400: Analog inputs

The hardware configuration of the sample project contains two analog inputs. The corresponding

Lenze Teachware case i700 contains a control panel for controlling the inputs of the I/O system.

• The sample project does not contain/require a pre-configured mapping of the analog inputs.

Advertising