3-4

Configuring the Adapter

• Setting Parameter 12 - [RcvHrtBeat Time] to “0” disables the fault

action, and a value greater than “0” enables the fault action. If
nviDrvSpeedStpt is not received by the adapter within the
Parameter 12 - [RcvHrtBeat Time] value, the fault action in
Parameter 06 - [Comm Flt Action] will be taken.

Changes to these parameters take effect immediately. A reset is not
required.

Parameter 09 - [Idle Flt Action] lets you determine the action of the
adapter and connected drive when the node is taken offline.

To change the idle fault action

• Set the value of Parameter 09 - [Idle Flt Action] to the desired

response action:

Figure 3.2 Idle Fault Action Screen on PowerFlex 4-Class HIM (22-HIM-*)

Changes to this parameter take effect immediately. A reset is not
required.

Setting the Idle Fault Action

Value

Action

Description

0

Fault

The drive is faulted and stopped. (Default)

1

Stop

The drive is stopped, but not faulted.

2

Zero Data

The drive is sent 0 for output data. This does not
command a stop.

3

Hold Last

The drive continues in its present state.

4

Send Flt Cfg

The drive is sent the data that you set in the fault
configuration parameters (Parameter 10 - [Idle Cfg
Logic]
and Parameter 11 - [Idle Cfg Ref]).

Idle Flt Action

Parameter:

#

009

Fault

0

VALUE

LIMITS

SEL

!