Configuring the Network

4-17

NCI: nciDrvSpeedScale

Format: SNVT_lev_percent

Explanation: This Network Configuration Input sets a default value to
nviDrvSpeedScale on every drive power cycle.

Valid Range: -163.000 to + 163.000%

Default Value: 0.000%

NCI: nciGenRdAdr

Format: SNVT_count

Explanation: This Network Configuration Input is used to read any
parameter in the drive. The data is read via the nvoGenRdData output.

Valid Range: Any 2-byte valid drive parameter that can be read with
Modbus command 03 (read holding register).

Default Value: 0 (not used)

Speed Setpoint Scaling Default Value

Generic Parameter Read Address