Rockwell Automation 22-COMM-L LonWorks Adapter User Manual
Page 37
Configuring the Network
4-9
Variable: nvoDrvVolt
Format: SNVT_volt
Explanation: This Network Variable Output provides the drive output
voltage in volts.
PowerFlex 40/400 Drive Parameter Equivalent: Parameter d004 -
[Output Voltage]
Variable: nvoDrvTemp
Format: SNVT_temp_p#US
Explanation: This Network Variable Output provides the drive
temperature in °F.
PowerFlex 40/400 Drive Parameter Equivalent: Parameter d024 -
[Drive Temp]
Variable: nvoFreqAct
Format: SNVT_freq_hz
Explanation: This Network Variable Output provides the drive output
frequency in Hz. This value is always positive (does not indicate the
forward/reverse direction of revolution).
PowerFlex 40/400 Drive Parameter Equivalent: Parameter d001 -
[Output Freq]
Drive Voltage
Drive Temperature
Output Frequency