Rockwell Automation 22-COMM-L LonWorks Adapter User Manual

Page 44

Advertising
background image

4-16

Configuring the Network

NCI: nciRampUpTm

Format: SNVT_time_sec

Explanation: This Network Configuration Input sets the acceleration
time. The value specifies the length of time it will take to bring the
inverter from stop to maximum frequency.

Valid Range: 0.0 - 600.0 seconds

Default Value: 10.0 seconds

PowerFlex 40/400 Drive Parameter Equivalent: Parameter P039 -
[Accel Time 1]

NCI: nciRampDownTm

Format: SNVT_time_sec

Explanation: This Network Configuration Input sets the deceleration
time. The value specifies the length of time it will take to bring the
inverter to a stop when running at maximum frequency.

Valid Range: 0.1 - 600.0 seconds

Default Value: 10.0 seconds

PowerFlex 40/400 Drive Parameter Equivalent: Parameter P040 -
[Decel Time 1]

NCI: nciLocation

Format: SNVT_str_asc

Explanation: This Network Configuration Input can be used to set the
physical location of the object in text. That is, it can hold the building,
level, and room descriptor. A maximum of 31 characters can be entered.

Default Value: Empty spaces

Ramp Up Time

Ramp Down Time

Location