Configuring the Adapter

3-5

To set the fault configuration parameters

If you set Parameter 06 - [Comm Flt Action] or 09 - [Idle Flt Action]
to the “Send Flt Cfg,” the values in the following parameters are sent to
the drive after a communications fault and/or idle fault occurs. You must
set these parameters to values required by your application.

Changes to these parameters take effect immediately. A reset is not
required.

Changes to switch settings and some adapter parameters require that you
reset the adapter before the new settings take effect. You can reset the
adapter by cycling power to the drive or by using the following
parameter:

• Set Parameter 03 - [Reset Module] to Reset Module.

Figure 3.3 Reset Screen on PowerFlex 4-Class HIM (22-HIM-*)

When you enter 1 = Reset Module, the adapter will be immediately
reset. When you enter 2 = Set Defaults, the adapter will set all adapter
parameters to their factory-default settings. After performing a Set
Defaults, enter 1 = Reset Module so that the new values take effect. The
value of this parameter will be restored to 0 = Ready after the adapter is
reset.

Parameter

Name

Description

07

Flt Cfg Logic

A 16-bit value sent to the drive for Logic Command.

08

Flt Cfg Ref

A 16-bit value (0 – 65535) sent to the drive as a Reference.

Resetting the Adapter

!

ATTENTION: Risk of injury or equipment damage exists. If the
adapter is transmitting control I/O to the drive, the drive may fault when
you reset the adapter. Determine how your drive will respond before
resetting a connected adapter.

Value

Description

0

Ready (Default)

1

Reset Module

2

Set Defaults

Reset Module

Parameter:

#

003

Ready

0

VALUE

LIMITS

SEL

!