background image

5-2

Troubleshooting

The Port status LED indicates the status of the DSI interface between the
adapter and the drive.

The MOD status LED reports the status of the communication adapter.

PORT Status Indicator

State

Cause

Corrective Actions

Off

The adapter is not powered or
is not connected properly to
the drive.

• Securely connect the adapter to the drive

using the Internal Interface ribbon cable.

• Apply power to the drive (or adapter if

mounted in a DSI External Comms Kit).

Flashing
Red

The adapter is not receiving a
communication from the drive
or the drive is faulted.

• Verify that cables are securely connected

and not damaged. Replace cables if
necessary.

• Cycle power to the drive (or adapter if

mounted in a DSI External Comms Kit).

Solid
Red

The drive is not an
Allen-Bradley drive.

• Verify that cables are securely connected

and not damaged. Replace cables if
necessary.

• Use Allen-Bradley PowerFlex 4/40/400

drives.

Flashing
Green

The adapter is establishing
communication with the drive.

No action required. This status indicator will
turn solid green or flashing red.

Solid
Green

The adapter is properly
connected and
communicating with the drive.

No action required.

MOD Status Indicator

State

Cause

Corrective Actions

Off

The adapter is not powered or
properly connected to the
drive.

• Securely connect the adapter to the drive

using the Internal Interconnect ribbon cable.

• Apply power to the drive (or adapter if

mounted in a DSI External Comms Kit).

Flashing
Green

The adapter is operational,
but is not transferring I/O
data.

Set adapter to Enabled and Online mode.

Solid
Green

The adapter is operational
and transferring I/O data.

No action required.

Flashing
Red

The adapter has detected a
communication error on the
Lon network.

• Verify that cables are securely connected

and not damaged. Replace cables if
necessary.

• Adjust the values of MinSendTime and

SendHeartBeatTime to match each other.

Advertising