4-10

Configuring the Network

Variable: nvoDrvRunHours

Format: SNVT_time_hour

Explanation: This Network Variable Output provides the drive total
running time in whole hours.

PowerFlex 40/400 Drive Parameter Equivalent: Parameter d018 -
[Elapsed Run Time]

Variable: nvoDCBusVolt

Format: SNVT_volt

Explanation: This Network Variable Output provides the DC Bus
voltage in volts.

PowerFlex 40/400 Drive Parameter Equivalent: Parameter d005 -
[DC Bus Voltage]

Variable: nvoDrvRunning

Format: SNVT_switch

Explanation: This Network Variable Output indicates if the drive is
running (active). It is the same status as read from bit 1 in nvoDrvStatus.

Operation Hour Counter

DC Bus Output

Drive Running

nvoDrvRunning Variable

Status

Value (%)

State

0.0

0

Not Active

100.0

1

Active