Rockwell Automation 22-COMM-L LonWorks Adapter User Manual

Page 61

Advertising
background image

Adapter Parameters

B-3

09

[Idle Flt Action]
Sets the action that the adapter will take during
offline/disable occurrences.

Default:

0 = Fault

Values:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Type:

Read/Write

Reset Required:

No

10

[Idle Cfg Logic]
Sets the Logic Command data that is sent to the
drive if Parameter 09 - [Idle Flt Action] is set to
“4 = Send Flt Cfg” and communications are
disrupted.

Refer to

Logic Command Word on page C-1

for

the bit definitions.

Default:

0000 0000 0000 0000

Minimum:

0000 0000 0000 0000

Maximum:

1111 1111 1111 1111

Type:

Read/Write

Reset Required:

No

11

[Idle Cfg Ref]
Sets the Reference data that is sent to the drive
if Parameter 09 - [Idle Flt Action] is set to
“4 = Send Flt Cfg” and communications are
disrupted.

This is a linear engineering unit value where “0”
equals 0 Hz. and “32767” equals the Hz. value in
the PowerFlex 40/400 Parameter P035 -
[Maximum Freq].

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read/Write

Reset Required:

No

12

[RcvHrtBeat Time]
Sets the time used as a Receive Heartbeat timer
and triggers the fault action in Parameter 06 -
[Comm Flt Action]
.

Default:

120.0

Minimum:

0.0 seconds

Maximum:

6553.0 seconds

Type:

Read/Write

Reset Required:

No

Parameter
No. Name and Description

Details

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 09 - [Idle
Flt Action]
lets you determine the action of the adapter and connected drive
when an offline/disable condition occurs. By default, this parameter faults the
drive. You can set this parameter so that the drive continues to run. Take
precautions to ensure that the setting of this parameter does not create a hazard
of injury or equipment damage. When commissioning the drive, verify that your
system responds correctly to various situations (for example, an idle controller).

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 06 -
[Comm Flt Action]
and Parameter 12 - [RcvHrtBeat Time] let you determine
the action of the adapter and connected drive if communications are disrupted.
Take precautions to ensure that the setting of these parameters does not create
a hazard of injury or equipment damage. When commissioning the drive, verify
that your system responds correctly to various situations (for example, a
disconnected cable).