Rockwell Automation 1336VT 5-300 AMP (2.2-160KW) User Manual
Page 103
Logic Interface Options
Appendix A
A-5
1336ĆMODĆL1
Terminal 22 and Interface Common
+5V DC TTL Logic Contact
Closure Interface Board (cont.)
Jog
True = Jog
False = Interrupt Jog and Allow Other Functions
This input will jog the drive if it is not running and interlocks permit. As
long as interlocks permit and the jog command remains True, the drive will
continue to run at the programmed jog frequency.
Terminal 23 and Interface Common
Reverse
Maintained True = Reverse
Maintained False = Forward
Parameter 22 enables the direction of drive rotation to be controlled by an
input at Terminal 23. A maintained False will select the forward direction,
a maintained True the reverse direction.
Terminal 24 and Interface Common
SW1
True = SW1 Function Selected
False = SW1 Function Not Selected
Parameters 26-31 and 72-76 define the SW1 function.
Terminal 26 and Interface Common
SW2
True = SW2 Function Selected
False = SW2 Function Not Selected
Parameters 26-31 and 72-76 define the SW2 function.