Specifications

Chapter 4

4-5

Output Power (cont.)

Boost:

11 selectable values from 0 to 48V DC peak.

– Adjustable from 0 to 115V DC through optional
programming.

– Independent Accel/Run Boost to minimize motor
heating while maximixing motor torque.

Accel/Decel:

Two independently programmable accel times.
Two independently programmable decel times.
Each time may be programmed over a range from
0 to 600 seconds.

Intermittent

Programmable MOPC from 50 to 115% of rated output

Overload Capability: current for up to 1 minute maximum.

Inverse Time

Designed to meet NEC and UL equivalent requirements.

Overload Capability: Adjustable timing from 50 to 115% of rated drive current

(Main Control Board Firmware Version 1.10 limited to 100%).

Drive

180% of rated output current.

Overcurrent Trip:

Ground Fault:

Detects drive output ground fault path by sensing
unbalanced bus or input line currents.

Table 4.4 Ċ 1336VT Output Current and kVA

Internal
Chassis

Component

Heatsink

Heat

Heat

Total

Minimum

Drive

kVA Out

kVA Out

kVA Out

Dissipation

Dissipation

Dissipation

CFM

Amps Out

Rating

380V AC

415V AC

460V AC

(BTU/hour) n

(BTU/hour) n

(BTU/hour) n

Required n

5.0

B003

3.3

3.6

4.0

119

171

290

15

8.0

B005

5.3

5.8

6.4

154

222

375

20

11.0

B007

7.2

7.9

8.8

239

375

614

32

14.0

B010

9.2

10.1

11.2

290

460

750

40

21.0

B015

13.8

15.1

16.7

409

1040

1449

75

27.0

B020

17.8

19.4

21.5

477

1228

1705

88

34.0

B025

22.4

24.4

27.1

495

1449

1944

100

40.0

B030

26.3

28.8

31.9

597

1620

2217

115

52.0

B040

34.2

37.4

41.4

767

2404

3171

165

65.0

B050

42.8

46.7

51.8

1006

2882

3887

200

77.0

B060

50.7

55.3

61.3

1159

3001

4160

215

96.0

B075

63.2

69.0

76.5

1398

3274

4672

241

124.0

B100

81.6

89.1

98.8

1773

5456

7229

375

156.0

B125

102.7

112.1

124.3

2114

8116

10230

527

180.0

B150

118.5

129.4

143.4

2387

8184

10571

545

240.0

B200

158.0

172.5

191.2

2933

12753

15686

810

300.0

B250

197.4

215.6

239.0

3171

14902

18073

932

n The above information is provided for reference only. For all ratings the user must verify that the selected enclosure will dissipate the total BTUs

generated within the enclosure without allowing the internal ambient to rise above 50

°

C. Enclosure mounting and location must allow for the heatsink

to extend outside the enclosure.

When locating the drive allow a minimum clearance from other components of 4.0 inches (101.6 mm) on the top and bottom, 2.0 inches (50.8 mm) on

either side.

When mounting the drive, ensure that the heatsink fins are vertical.

With the heatsink exposed to the ambient, the drive will dissipate heat as listed in the Output Current Table above.