Drive enclosure type, Factory installed options – Rockwell Automation 1336VT 5-300 AMP (2.2-160KW) User Manual

Page 16

Advertising
background image

Drive and Option Identification

Chapter 2

2-2

The second, third and fourth characters indicate the power rating of the
drive, as shown in Table 2.1.

Table 2.1 - 1336VT Output Current and kVA

Rating

Amp

kVA Out

kVA Out

kVA Out

Code

Out

380V AC

415V AC

460V AC

003

5.0

3.3

3.6

4.0

005

8.0

5.3

5.8

6.4

007

11.0

7.2

7.9

8.8

010

14.0

9.2

10.1

11.2

015

21.0

13.8

15.1

16.7

020

27.0

17.8

19.4

21.5

025

34.0

22.4

24.4

27.1

030

40.0

26.3

28.8

31.9

040

52.0

34.2

37.4

41.4

050

65.0

42.8

46.7

51.8

060

77.0

50.7

55.3

61.3

075

96.0

63.2

69.0

76.5

100

124.0

81.6

89.1

98.8

125

156.0

102.7

112.1

124.3

150

180.0

118.5

129.4

143.4

200

240.0

158.0

172.5

191.2

250

300.0

197.4

215.6

239.0

Drive Enclosure Type

The first character “E” indicates enclosure code.

The second character indicates the type of enclosure as initially shipped
from the factory.

O

–– Open style (IP00)

A

–– NEMA Type 1 (IP20)

The third character indicates enclosure size by amp rating.

N

–– 5.0, 8.0, 11.0, 14.0 or 21.0 Amp ratings

P

–– 27.0 or 34.0 Amp ratings

R

–– 40.0 or 52.0 Amp ratings

S

–– 65.0 or 77.0 Amp ratings

T

–– 96.0, 124.0, 156.0 or 180.0 Amp ratings

W

–– 240.0 or 300.0 Amp ratings

Factory Installed Options

All additional characters indicate drive options that were initially installed
at the factory. Each option code is added to the catalog number and
separated by a hyphen.

Advertising