Terminal block tb1 - 5ć52ăamp power wiring (cont.), Maximum wire size and torque requirements – Rockwell Automation 1336VT 5-300 AMP (2.2-160KW) User Manual

Page 51

Advertising
background image

Wiring

Chapter 6

6-7

Terminal Block TB1 -

5Ć52ĂAmp Power Wiring (cont.)

Power

Drive

Maximum

Rating

Output

Wire

Wire

Maximum

Code

Current

Group

n

Size

C

Torque

c

003

5 Amps

2

6 AWG

20 In-lbs

005

8 Amps

2

6 AWG

20 In-lbs

007

11 Amps

2

6 AWG

20 In-lbs

010

14 Amps

2

6 AWG

20 In-lbs

015

21 Amps

2

6 AWG

20 In-lbs

020

27 Amps

2

6 AWG

20 In-lbs

025

34 Amps

2

6 AWG

20 In-lbs

030

40 Amps

2

6 AWG

20 In-lbs

040

52 Amps

2

6 AWG

20 In-lbs

n

Wire group number chart, page 6-3.

C

16 mm

2

.

c

2.26 N-m.

Maximum Wire Size and Torque Requirements

Use the following guidelines when selecting branch circuit protection.

5 Amp Drive

Fuse Size 10A

Fuse Type KTK-R, JJS or Equivalent

8 Amp Drive

Fuse Size 15A

Fuse Type KTK-R, JJS or Equivalent

11 Amp Drive

Fuse Size 20A

Fuse Type KTK-R, JJS or Equivalent

14 Amp Drive

Fuse Size 25A

Fuse Type A4J, JJS or Equivalent

21 Amp Drive

Fuse Size - A

Fuse Type A4J -30, JJS -35 or Equivalent

27 Amp Drive

Fuse Size 45A

Fuse Type A4J, JJS or Equivalent

34 Amp Drive

Fuse Size 60A

Fuse Type A4J, JJS or Equivalent

40 Amp Drive

Fuse Size - A

Fuse Type A4J -60, JJS -70 or Equivalent

52 Amp Drive

Fuse Size 80A

Fuse Type A4J, JJS or Equivalent