Terminal block tb1 - 5ć52ăamp power wiring (cont.), Maximum wire size and torque requirements – Rockwell Automation 1336VT 5-300 AMP (2.2-160KW) User Manual
Page 51
Wiring
Chapter 6
6-7
Terminal Block TB1 -
5Ć52ĂAmp Power Wiring (cont.)
Power
Drive
Maximum
Rating
Output
Wire
Wire
Maximum
Code
Current
Group
n
Size
C
Torque
c
003
5 Amps
2
6 AWG
20 In-lbs
005
8 Amps
2
6 AWG
20 In-lbs
007
11 Amps
2
6 AWG
20 In-lbs
010
14 Amps
2
6 AWG
20 In-lbs
015
21 Amps
2
6 AWG
20 In-lbs
020
27 Amps
2
6 AWG
20 In-lbs
025
34 Amps
2
6 AWG
20 In-lbs
030
40 Amps
2
6 AWG
20 In-lbs
040
52 Amps
2
6 AWG
20 In-lbs
n
Wire group number chart, page 6-3.
C
16 mm
2
.
c
2.26 N-m.
Maximum Wire Size and Torque Requirements
Use the following guidelines when selecting branch circuit protection.
5 Amp Drive
Fuse Size 10A
Fuse Type KTK-R, JJS or Equivalent
8 Amp Drive
Fuse Size 15A
Fuse Type KTK-R, JJS or Equivalent
11 Amp Drive
Fuse Size 20A
Fuse Type KTK-R, JJS or Equivalent
14 Amp Drive
Fuse Size 25A
Fuse Type A4J, JJS or Equivalent
21 Amp Drive
Fuse Size - A
Fuse Type A4J -30, JJS -35 or Equivalent
27 Amp Drive
Fuse Size 45A
Fuse Type A4J, JJS or Equivalent
34 Amp Drive
Fuse Size 60A
Fuse Type A4J, JJS or Equivalent
40 Amp Drive
Fuse Size - A
Fuse Type A4J -60, JJS -70 or Equivalent
52 Amp Drive
Fuse Size 80A
Fuse Type A4J, JJS or Equivalent