Startup
Chapter 9
9-4
Initial Operation
Step 9a
- Motor Disconnected (cont.)
The P
R
portion of the Programming and Display Panel will indicate the
speed source currently being used. Verify that the drive will accept the
required speed reference sources.
Freq
P
R
Are preset speeds to be used?
No – Go to Step 9b.
Yes – Select preset Speed 1.
Select preset Speed 5.
Display must be - 7.
Display must be - 9.
Select preset Speed 2.
Select preset Speed 6.
Display must be - 8.
Display must be - 9.
Select preset Speed 3.
Select preset Speed 7.
Display must be - 9.
Display must be - 9.
Select preset Speed 4.
Display must be - 9.
Open all preset speed inputs.